Connect the Outdoor Unit with Connecting Pipe:
Aim the counter-bore of the connecting pipe at the stop valve, and
tighten the Taper nut with fingers. Then tighten the Taper nut with
a torque wrench. When prolonging the piping, extra amount of
refrigerant must be added so that the operation and performance of
the air conditioner will not be compromised.
Note: 1. This table is for reference only.
2. The joints shall not be reused, unless after re-flaring the pipe.
3. After installation, check the stop valve cover whether be fixed effectively.
INSTALL OUTDOOR UNIT
GAS R32
Dimension drawing of outdoor unit installation
Install the connection pipe
Installation outdoor unit bolt
Space to the obstruction
Space to the obstruction
Space to the obstruction
Air inside
Air outside
50cm above
50cm above
30cm above
200cm above
10cm above
Left
installation feet
Right
installation feet
Air inlet
Air outlet
Outdoor Unit Size of Shape
W1(W2) x H x D (mm)
A (mm)
B (mm)
665(710)x420x280
430
280
600(645)x485x260
400
290
660(710)x500x240
500
260
700(745)x500x255
460
260
730(780)x545x285
540
280
760(810)x545x285
540
280
790(840)x550x290
545
300
800(860)x545x315
545
315
800(850)x590(690)x310
540
325
825(880)x655x310
540
335
900(950)x700x350
630
350
900(950)x795x330
535
350
970(1044)x803x395
675
409
Piping
length
Amount of refrigerant to be added
Amount of
refrigerant for
the unit
5M
Not needed
5-15M
CC12000Btu
16g/m
1 kg
CC18000Btu
24g/m
2 kg
Connection
pipe
Liquid side pipe
Gas side pipe
Spanner
Stop valve
cover
Taper nut
Stop valve