SNMP traps are sent if:
•
event occurs (status change) on Digital Input 1 or Digital Input 2;
•
measured voltage on Analog Input 1 or Analog Input 2 goes outside the range;
•
measured temperature goes outside the range;
•
measured humidity goes outside the range;
•
restart condition.
8.5.
I/O setup page
I/O settings can be made here. For temperature, humidity and analog value MIN, MAX, and
HYSTERESIS values can be set. These values define the thresholds for all monitored parameters.
When the measured value goes out of range SNMP trap or e-mail (if enabled) will be sent.
Leaving range is considered when the parameter goes lower than MIN values or higher than
MAX. Coming back in the range is considered when the parameter goes higher than (MIN +
HYSTERESIS) or lower than (MAX – HYSTERESIS).