Control and monitoring using SNMP
TCW122B-CM can be configured and monitored through SNMP (Simple Network Management
Protocol). This could be done using every SNMP v.1 compatible program. Parameters that can be
changed, are grouped according to their functions in the tables below. To obtain a valid OID
number it is necessary to replace the “x” symbol with ”1.3.6.1.4.1.38783”. To save the changes
configurationSaved
(OID x.3.13.0) should be set to "1".
11.1.
Product
OID
Name
Access
Description
Syntax
x
.1.1.0
name
read-only Device name
String
x
.1.2.0
version
read-only Firmware version
String
x
.1.3.0
date
read-only Release date
String
11.2.
Setup -> network
OID
Name
Access
Description
Syntax
x.2.1.1.0
deviceIPAddress
read-write Device IP address
IpAddress
x.2.1.2.0
subnetMask
read-write Subnet Mask
IpAddress
x.2.1.3.0
gateway
read-write Gateway
IpAddress
x.2.1.4.0
deviceMACAddress
read-write Device MAC Address
OCTET STRING (SIZE(6))
x.2.1.5.0
dhcpConfig
read-write DHCP configuration ON/OFF
INTEGER { off(0), on(1) }
x.2.1.6.0
dns
read-write Domain Name Server address
IpAddress
x.2.1.7.0
Hostname
read-write Device hostname
String (SIZE (0..38))
11.3.
Setup
->
snmpSetup
OID
Name
Access
Description
Syntax
x.2.4.1.0
snmpConfiguration
read-write SNMP Configuration
INTEGER { disabled(0), enabled(1) }
x.2.4.2.0
trapEnabled
read-write TRAP messages ENABLED/DISABLED
INTEGER { no(0), yes(1) }
x.2.4.3.0
trapReceiverIPAddress
read-write TRAP receiver IP address
IpAddress
x.2.4.4.0
trapCommunity
read-write TRAP community
String (SIZE (0..13))
x.2.4.5.0
trapInterval
read-write TRAP messages interval
INTEGER (1..253)
x.2.4.6.0
maxNumberOfTraps
read-write Maximum number SNMP traps
INTEGER (1..253)
11.4.
Setup
->
oneWireSensor1
->
temperature1
OID
Name
Access
Description
Syntax
x.2.5.1.1.0
temperature1Min
read-write Temperature1 range (min. value)
INTEGER (-400..1250)
x.2.5.1.2.0
temperature1Max
read-write Temperature1 range (max. value)
INTEGER (-400..1250)
x.2.5.1.3.0
temperature1Hyst
read-write Hysteresis
INTEGER (0..1250)
x.2.5.1.4.0
temperature1Action
read-write Temperature1 action
INTEGER {
noAction(0), sendMail(1) }
11.5.
Setup
->
oneWireSensor1
->
humidity1
OID
Name
Access
Description
Syntax
x.2.5.2.1.0
humidity1Min
read-write Humidity1 range (min. value)
INTEGER (0..1000)
x.2.5.2.2.0
humidity1Max
read-write Humidity1 range (max. value)
INTEGER (0..1000)
x.2.5.2.3.0
humidity1Hyst
read-write Hysteresis
INTEGER (0..1000)
x.2.5.2.4.0
humidity1Action
read-write Temperature1 action
INTEGER {
noAction(0), sendMail(1) }