background image

3.  PURPOSE

 

 

 

Explosion proof pendant lighting fitting / light switch, type PLFM ...-. is intended for general lighting in industrial with potentially 
explosive atmosphere of gases, vapors and dust in zones 1, 2, 21, 22 in accordance with EN 60079-10-1 and EN 60079-10-2.

 

 
4.  PRODUCT COMPLIANCE

 

 

Design of lighting fitting is accordance with the standard EN 60598-1 and all related standards. 
The product is in compliance with Regulations concerning equipment and protective systems for use in potentially explosive 
atmosphere. 
The product complies with the ATEX Directive 2014/34/EU and standards: 

-

 

EN IEC 60079-0:2018, 

-

 

EN 60079-1:2014, 

-

 

EN IEC 60079-7:2015/A1:2018, 

-

 

EN 60079-31:2014. 

The product has been developed, manufactured and tested according to the existing state of technique accordance with the 
standards EN 9001, EN ISO 80079-34 and EN ISO 14001. 
The product is in compliance with the LV Directive 2014/35/EU. 
The product is in compliance with the RoHS Directive 2011/65/EU. 
The product is in compliance with EMC Directive 2014/30/EU. 

 
5.  DEGREE OF PROTECTION AND DATA 

 

Certificate: 

FIDI 19 ATEX 0047 

Category and  
explosion protection: 

 

II 2G Ex db eb IIC T6-T3 Gb ili II 2G Ex db IIC T6-T3 Gb 
II 2D Ex tb IIIC T85°C – T155°C Db 

Ambient temperature: 

-20ºC ≤ T

≤ +40°C 

Mechanical protection: 

IP66, category 1 

Resistance to shock: 

IK 08 

Class of protection: 

I (PE - protective earthing) 

Rated voltage: 

-230 V (-10%  /  +6%) / 50 Hz 
- PLFM FLASH, PLFM LUXOMAT- . see Table of light sources

 

Rated power: 

- see Table of light sources

 

Luminous flux  

- see Table of light sources

 

Wiring: 

-  Radox  155  or  Betatherm  155,  IEC  60228:2005  IEC  60228:2005  class  5, 
1,5mm

2

                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                    

Connection  terminals  inside  housing  /  light 
switch: 

- tree-pole plug and socket

 

terminals for connection L + N + PE; 2,5mm

2

 

max, solid, stranded 
- four-pole plug and socket

 

terminals for connection L + L’ + N + PE; 

2,5mm

2

  max, solid, stranded 

Connection terminals inside Ex eb / tb 
junction box / light switch: 

- conductor terminals for connection of phase, neutral and protective 

conductor L + L '+ N + PE; 2.5mm2 single-wire, multi-wire 

- true wiring is also possible by connecting two conductors to the same 

terminal inside the Ex eb connection chamber, 2.5mm2 max. 

Ex eb / tb cable glands and plugs 
 

- two Ex eb / tb SPU 25 cable glands ISO 25  II 2G Ex eb IIC Gb  
II 2D Ex tb IIIC Db for diameter cable Ø7-15 mm in accordance EN 62444 
Certificate: FIDI 19 ATEX 0003X  
-  two  Ex  eb  /  tb  TEPEx  plugs,  II  2G  Ex  eb  IIC  Gb  II  2D  Ex  tb IIIC  Db  in 
accordance EN 62444 
Certificate: FIDI 19 ATEX 0003 

Connection terminals inside Ex db eb/tb 
adapter ADP 23/1: 

- terminals for connection L + N + PE; 2,5 mm

2

,  

- solid, stranded 

Connection terminals inside Ex db eb/tb 
adapter ADP 24/1: 

- terminals for connection L + N + PE; 2,5 mm

2

,  

- solid, stranded 

Adapter ADP: 

- type ADP 23/1, ADP 24/1, II 2G Ex db eb IIC Gb  II 2D Ex tb IIIC Db, 
 for cable  

v

 7-15 mm 

Certificate: FIDI 19 ATEX 0014X 

Connection cable for direct entry via  
Ex db / tb cable entries: 

- connection on tree-pole / four-pole plug inside housing for connection  
 L + N + PE; 2,5mm

2

 solid, stranded 

Ex db / tb cable gland: 

- ATEX certified II 2G / D Ex db / tb IP66 M20 cable gland 

 
 

0722

Summary of Contents for PLFM 100 Series

Page 1: ...re off implement this user manual can reduce explosion protection and endanger people property and the environment Any improper and illegal actions as well as non compliance with the provisions of this user manual excludes all responsibility by manufacturer side Before installation commissioning Carefully read all instructions Execute proper training of responsible personnel Check that the content...

Page 2: ...ble of light sources Rated power see Table of light sources Luminous flux see Table of light sources Wiring Radox 155 or Betatherm 155 IEC 60228 2005 IEC 60228 2005 class 5 1 5mm2 Connection terminals inside housing light switch tree pole plug and socket terminals for connection L N PE 2 5mm2 max solid stranded four pole plug and socket terminals for connection L L N PE 2 5mm2 max solid stranded C...

Page 3: ...a lower pulling force in accordance with p A 3 1 1 of EN IEC 60079 0 the device must be installed in places with a lower risk of impact because the multi core conductive insulator with a connection chamber has been tested with a lower impact energy in accordance with EN IEC 60079 0 Threaded joints M125x1 5 6H 6g medium tolerance according to ISO 965 3 thread DIN 13 T 24 11 full threads M20x1 5 6H ...

Page 4: ...5900 lm Osram 5600 lm Philips E27 T4 130 C Vialox NAV E 70W I SON 70W I E27 CO 1CT 50W HSE 230 V 50 Hz 3600 lm Osram 3500 lm Osram E27 T4 130 C Vialox NAV E 50W I SON 50W I E27 CO 1CT PLFM LUXOMAT 10 12 V AC DC T6 85 C Doepke DASY 010 24 V AC DC 230 V AC PLFM LUXOMAT 16 230 V AC T6 85 C Doepke DASY 016 7 MOUNTING AND INSTALLATION Mounting of the lamp With vertical suspension on the bolt with ring ...

Page 5: ...and users Regulations and includes supervision of parts on which the explosion protection depends especially that the housing all part of housing replacement glass and gaskets without rupture and damage that the housing completely closed with replacement glass compound and that mechanical blockage against self opening is done that the cable gland plug adapter pressure nut of cable gland screws cov...

Page 6: ...n of conformity becomes invalid 10 SPARE PART AND ACCESSORIES SKETCH DESCRIPTION CODE SKETCH DESCRIPTION CODE Replacement glass PLFM PLFM 10 120 plug and socket terminals PLFM 10 180 Gasket PLFM PLFM 10 140 Adapter ADP 23 1 PLFM 20 110 Heat sink SET PLFM PLFM 10 180 Ex e cable gland SPU 25 SPU 25 Lamp holder PLFM PLFM 10 150 Ex eb plug SPC 25 SPC 25 Ballast SET PLFM PLFM 10 170 Ex db cable gland L...

Page 7: ...ctive 1999 92 EC ATEX 137 The responsible person shall ensure their implementation at the working facility 12 STORAGE AND TRANSPORT Transportation and warehousing of the lamps is only allowed in the original packaging as outlined in a cardboard box 13 MANUFACTURER S WARRANTY The manufacturer provides a warranty on the product for a period of one year under the provisions of this user manual and th...

Page 8: ... natpisnom pločicom na kućištu tip PLFM 70 HSE 3 marking plate with technical data on housing and inside housing ...