23
KADEME OLCUMU
Menu.2.2
Settings
E
Step Menu
E
Automatic Step Measurement Period
The capacitors connected at the stages experience a decrease in their capacities depending
on the frequency of use and time. With this parameter, it is aimed that the current values of the
capacitors can be learned by the device at certain time intervals and the device can intervene
more precisely.
At the end of the set period, the device will automatically measure and record all steps in the
system and perform its intervention according to the current step values.
It is the seventh of 7 different setting parameters in the step values m
enu. To change the Automatic
Step Measurement Period, press the SET button while the Automatic Step Measurement Period page
is on the screen.
You can use UP / DOWN buttons to change the current value. Press the SET button to save.
AUTOMATIC STEP
MEASUREMENT PERIOD
Menu.2.7
Step Measure. Period
Period : 0 Week
Period Passive
Menu.2.7.1
Settings
E
Advanced Settings Menu
It is the third menu that appears when you proceed by
pressing the UP button after entering the settings page. In this
menu, Compensation Target Value can be set, Power Analysis
Samples can be viewed, ModBus Communication settings can
be made, Operating Voltage and Working Harmonics can be
set, Records can be deleted, Generator Compensation and
Compensation Alarm settings can be made.
To enter the Advanced Settings Menu, press the SET button while the Advanced Settings
Menu page is on the screen. Use UP and DOWN buttons to access other settings in the menu.
ADVANCED SETTINGS
MENU
Menu.3.0
It is the first of the 8 different setting parameters in the advanced settings menu. To change
the Power Factor Correction Settings, press the SET button with the Power Factor Correction
page on the screen.
To change the current value, the relevant parameter must be selected with the RIGHT button.
The selected parameter is indicated by the "
>
" sign on the left side.
PF Correction
>Set : 5%
Cos:0.9988 Induct.
Tolerance: % 1.0
Menu.3.1.1
Settings
E
Advanced Settings Menu
E
Power Factor Correction
POWER FACTOR
Menu.3.1
CORRECTION
24
Set:
The targeted compensation set value is entered here. Inductive or Capacitive set can be
entered. The Cosinus value that will occur as a result of the entered set value appears at the
bottom of the screen.
Tolerance:
It is the movement area that will be given to the device in an inductive and
capacitive direction in order to ensure less activation / passivation to extend the lifetime of the
contactors, capacitors and reactors in the stages. The device will not change its current
response for reactive power changes within the SET ± Tolerance value in this field.
Example:
If the SET value is 0% (Cos: 1) and the Tolerance value is 2%, the device will not
change its current response for reactive power changes within this area after reaching a ratio
between Inductive 2% and Capacitive 2%.
SAMPLE: 1
L1: -100.00 kVAr
L2: -100.00 kVAr
L3: -100.00 kVAr
Sample Time:10000 min
Menu.3.2.1
Settings
E
Advanced Settings Menu
E
Power Analysis Samples
It is the second of 8 different setting parameters in the advanced settings menu. To view the
Power Analysis Samples, press the SET button while the Power Analysis Samples page is on the
screen.
In this page, reactive powers drawn from each phase are recorded along with their duration.
(capacitive powers are indicated by a (-) sign.)
If the power consumption remains constant over a certain period of time, it is recorded as an
sample. If the next sample is 15% above the previous one, it will be saved as a different one. If
the under 15%, only the duration is added to the previous example. Contains a total of 20
samples. It can take samples for up to 9999 minutes.
You can use the UP / DOWN buttons to navigate through the samples.
You can review Page 31 for detailed explanation.
(
Step Value Determination According to
Power Analysis Examples.
)
POWER ANALYSYS
SAMPLES
Menu.3.2
It is the third of the 8 different setting parameters in the advanced settings menu. To change
the ModBus RS485 Settings, press the SET button while the ModBus RS485 page is on the screen.
In this page, you can navigate between parameters (Baudrate, Parity, Stop Bit and ModBus ID)
with the RIGHT button, and change the value in the selected parameter with the UP / DOWN buttons.
To change the current value, the relevant parameter must be selected with the RIGHT button.
The selected parameter is indicated by the "
>
" sign on the left side.
Settings
E
Advanced Settings Menu
E
ModBus RS485 (Communication Settings)
MODBUS RS485
Menu.3.3
Modbus Settings
>Baudrate: 9600 bps
Parity : No
Stop Bit: 1
Mbus ID : 1
Menu.3.3.1