Screen Description
9
1
2
3
4
5
1- Stage Leds:
The LEDs are lit when the steps are active.
2- Alarm Led:
It is the LED that lights to alert the user in case of alarm.
3- Graphic LCD:
It is the screen where all measurements, settings and notifications related to the
device are transferred to the user.
4- Status Leds:
Reactive/Active instant rate status and communication notification leds.
COM Led (Communication):
This LED is on during ModBus RTU communication.
IND Led (Inductive):
This LED will light if the inductive/active instantaneous rate is more than 20%.
CAP Led (Capacitive):
If the capacitive/active instantaneous rate is more than 15%, this led will light.
NOR Led (Normal):
Inductive/Active instantaneous rate less than 20% and Capacitive/Active
instantaneous rate less than 15% If it is low, this led will light.
4- Buttons:
They are used to monitor measurements and make adjustments.
ESC Button:
When pressed in the menu, it returns to the upper menu without saving the values. When
pressed outside the menu (on the measurement screens), always displays the Main measurement screen.
SET Button:
Enters the menu/parameter. By saving the change in the parameter exits the parameter.
UP Button:
It provides fast progress between the measured values outside the menu. Increases
the selected value while inside the parameters of the menu.
DOWN Button:
It provides fast progress between the measured values outside the menu.
Decreases the selected value while inside the parameters of the menu.
RIGHT Button:
When out of the menu, it provides the progress between the measurement values b y showing
the measured values t ogether with the details. It enables to switch between parameters while in the menu.
10
How to Install the Device?
Enter Password!
PASS : 0000
Three-phase capacitor equivalent to 1/40 of current
transformer ratio must be connected in the first three steps
for current transformer test to be performed. Also, the
current transformer connected to the device and the phase
order of the voltages must be the same. Otherwise, the device
will give phase inverse or step low warning. After fixing the
connection errors according to the warnings, you can start
the device setup again.
When SET button is pressed on any measurement page, the
PASSWORD page is displayed for entering the menu.
While on this page, press the SET button to enter the menu.
(The password value is “0000” by default. If the password
has been changed by the user, the password determined by
the user must be used to enter the menu.)
After passing the password page, Current Transformer
Menu page will be displayed on the screen.
While on this page, press SET button to enter Current
Transformer Menu.
The Current Transformer Test page will appear on the
screen. Press the UP button to switch to the Current
Transformer Value page.
While in this page, press the SET button to enter the
Current Transformer Value in the system.
Current Transformer Value Entry page will be displayed on
the screen.
While on this page, use the UP and DOWN buttons to enter
the Current Transformer Value in the system and then press
the SET button to save.
The device will automatically start Current Transformer
Test operation.
CURRENT TRANSFORMER
Menu.1.0
MENU
CURRENT TRANSFORMER
VALUE
Menu.1.2
Current Trans. Value
CTR: 1500 / 5A
Menu.1.2.1
Current Trans.Test(A)
1.Trial
Esc:Cancel
L1:0.000
L2:0.000
Plase Wait!
L3:0.000
In case of any problems in the connections, the device will
give a warning and will not accept the connection.
When current transformer test is successful, this page will
be displayed on the screen.
If the operation is confirmed by pressing the SET button, the
device will automatically start the Step Measurement process.
After the test, it indicates that the current transformer
terminals indicated with “(-)” are connected reversely. You
don't need to fix the links. The device will fix these
connections software-wise.
Current Trans.Test(A)
Contact Learned
k1-l1:(-)
k2-l2:(+)
k3-l3:(+)
Esc:Cancel Set:OK