15
How to Enter the Step Value Manually?
When you enter the Step Menu page, the Step Values page
is displayed on the screen first.
Switch to the Manual Step Value Set page by pressing the
UP button, then enter the Manual Step Value Set page by
pressing the SET button.
In this page, you can navigate between parameters (Step,
Type and Value) with the RIGHT button, and change the value
in the selected parameter with the UP/DOWN buttons.
To change the current value, the relevant parameter must
be selected with the RIGHT button. The selected parameter is
indicated by the sign "
>
" on the left side.
MANUAL STEP
VALUE SET
Menu.2.6
Enter Step Value
Type : L123
Value : -10.00kvar
>Step : 1
Menu.2.6.1
After entering the step information manually, SET button is
pressed to save. After the saving process, the step
information recorded and “Step Approved” are displayed on
the screen.
To exit without saving, pressing the ESC button will return
to the Maneul Step Value Set page.
Enter Step Value
Type : L123
Value : -10.00kvar
>Step : 1
Menu.2.6.1
Step Approved
Example:
On the screen above, the three-phase 10kVAr capacitor value has been entered in the 1st step.
If the value to be entered is single phase, “L1, L2 or L3” should be selected from the phase part
according to the phase to which it is connected. If the value to be entered is two phase, “L12, L23 or L31”
should be selected from the phase part according to the phase to which it is connected. If the value to be
entered is three phase, “L123” should be selected.
Note:
Capacitor values a re entered as (-) signed with DOWN button. Shunt reactor values a re entered
unsigned with the UP button.
When SET button is pressed on any measurement page, the
PASSWORD page is displayed for entering the menu.
While on this page, press the SET button to enter the menu.
(The password value is “0000” by default. If the password
has been changed by the user, the password determined by
the user must be used to enter the menu.)
After passing the password page, Current Transformer
Menu page will be displayed on the screen.
While on this page, press UP button to switch to the Step
Menu page.
The Step Menu page will appear on the screen. Press the
SET button to enter the Step Menu page.
STEP MENU
Menu.2.0
Enter Password!
PASS : 0000
16
How is Step Control Done?
It is a menu designed to control the connections and
robustness of the shunt reactors, capacitors and contactors
connected to the stages.
When SET button is pressed on any measurement page,
the PASSWORD page is displayed for entering the menu.
While on this page, press the SET button to enter the menu.
(The password value is “0000” by default. If the password
has been changed by the user, the password determined by
the user must be used to enter the menu.)
After passing the password page, Current Transformer
Menu page will be displayed on the screen.
While on this page, press UP button to switch to the Step
Menu page.
The Step Menu page will appear on the screen. Press the
SET button to enter the Step Menu page.
When you enter the Step Menu page, the Step Values page
is displayed on the screen first.
Switch to the Step Control page by pressing the UP button,
then enter the Step Control page by pressing the SET button.
In this page, you can navigate between the steps with UP /
DOWN buttons, you can use the RIGHT button to control /
activate the steps and passive the active steps.
Active steps are indicated by the "*" sign.
When you return to the measurements screen by pressing
the ESC button, if there are any steps you have activated
manually, the device will make these steps passive one by one.
Measurement Screen Introduction
Measurements
E
L1:220.0 L1:380.0
L2:220.0 L2:380.0
L3:220.0 L3:380.0
_____________________
TCR
%
R:23 S:23 T:23
Voltage(V) Curr.(A)
1
2
3
1- The area where the name and unit
of the measured value are specified.
2- The area where the measured values
are displayed.
3- The area where the SVC (TCR) usage
percentage and Alarm states are displayed.
NOTE.:
While the generator in the system is
activated, “GEN” * will appear on the screen
instead of “TCR”. (*: It is valid when the
generator is connected to the device.)
While on any measurement screen, you can switch to other measurement screens by using
UP / DOWN or RIGHT buttons.
STEP CONTROL
Menu.2.5
>01[*] 05[ ] 09[ ]
02[ ] 06[ ] 10[ ]
03[ ] 07[ ] 11[ ]
TCR[ ]
04[ ] 08[ ] 12[ ]
Menu.2.5.1 Control
STEP MENU
Menu.2.0
Enter Password!
PASS : 0000