background image

Figure-72

Hz

    Pr.41: High Frequency Protection Value 

Determines the maximum operating 

frequency value of load.

Default:

 51Hz,  

Min:

 45.0Hz,  

Max:

 70.0Hz  

Figure-82

Figure-81

Figure-79

Figure-78

Figure-77

Hz

Figure-76

Figure-75

Hz

Figure-73

Figure-28

Şekil-71

-13-

    

Pr.40: Demurrage Protection Factor

: Demurrage current is 3-5 times more than 

normal operation current consumption.

Ex:

 High current set value is :5A, demurrage protection factor is :1.5.

Max Demurrage current is 5x1.5=7.5 A so device will let motor use 35A for start up.

Default:

 3.0,  

Min:

 1.0,  

Max:

 10.0.

Esc

Set

13.3 - Frequency Settings:

Figure-72

Hz

Figure-74

Figure-80

Hz

    Press Menu button and enter password to enter program list. The figure-26(Voltage SET) is displayed 

when you enter password and press the Menu button. The figure-27(Current SET) is displayed when you 

press the up button. The figure-28(Frequency SET) is displayed when you press the up button. You enter 

Frequency set when you press Menu button. If you enter Frequency set menu, the figure-72(Pr.41) displayed. 

This menu have 11 different current set value. When you press the up button to see the other Frequency set 

values on the display, the next data is displayed. The figure-Figure 78 is displayed when you press the up 

button after the Pr.51 is displayed. By using up-down  buttons select the program. Press Menu to enter 

required program. By up-down buttons, you can set the program. Press Menu to record your settings, if you 

press ESC button, you cannot record your settings.

Pr.41: 

High Frequency Protection Value

Pr.42: 

High Frequency Protection Delay 

T

ime

Pr.43:

 

High Frequency Protection Reset 

T

ime

Pr.44:

 

High Frequency Protection Hysteresis 

Pr.45:

 

High Frequency Protection Enable/Disable

Pr.46: 

Low Frequency Protection Value

Pr.47:

 

Low Frequency Protection Delay 

T

ime

Pr.48:

 

Low Frequency Protection Reset 

T

ime

Pr.49:

 

Low Frequency Protection Hysteresis 

Pr.50:

 

Low Frequency Protection Enable/Disable

Pr.51: 

Frequency Auto Reset Enable/Disable

    

Pr.42: High Frequency Protection Delay Time:

 Determines delay open time. Delay 

time for activating the output. If any frequency exceeds high frequency protect value, 

Relay output switches open at the end of delay time.

Default:

 3sec,  

Min:

 1sec,  

Max:

 10000sec.

Figure-73

Figure-74

    

Pr.43: High Frequency Protection Reset Time:

 Determines delay close time. If all 

frequency below the high frequency protect value as a hysteresis frequency, relay output 

switches close at the end of the reset time.

Default:

 3sec,  

Min:

 1sec,  

Max:

 10000sec.

    Pr.44: High Frequency Protection Hysteresis:

 

Required hysteresis frequency for high 

frequency warning is programmed.

Default:

 0.5Hz,  

Min:

 0.1Hz,  

Max:

 20.0Hz  

 

Figure-75

Hz

Figure-79

Figure-78

Figure-77

Hz

Figure-76

-14-

   

Pr.45: High Frequency Protection Enable/Disable:

 Determines Enable or Disable the 

high frequency protection.

Default:

 Disable,  

Min:

 Disable,  

Max:

 Enable

    

Pr.50: Low Frequency Protection Enable/Disable :

 Determines Enable or Disable the 

low frequency protection.

Default:

 Disable,  

Min:

 Disable,  

Max:

 Enable

    Pr.46: Low Frequency Protection Value:

 

Determines the minimum operating 

frequency value of load.

Default:

 49Hz,  

Min:

 45.0Hz,  

Max:

 70.0Hz  

    

Pr.47: Low  Frequency Protection Delay Time

: Determines delay open time. Delay 

time for activating the output. If any frequency over the low frequency protect value, 

Relay output switches open at the end of delay time.

Default:

 3sec,  

Min:

 1sec,  

Max:

 10000sec.

    

Pr.48: Low Frequency Protection Reset Time:

 Determines delay close time. If all 

frequency below the low frequency protect value as a hysteresis frequency, relay output 
switches close at the end of the reset time.

Default:

 3sec,  

Min:

 1sec,  

Max:

 10000sec.

Hz

Figure-80

    Pr.49: Low Frequency Protection Hysteresis:

 

Required hysteresis frequency for low 

voltage warning is programmed.

Default:

 0.5Hz,  

Min:

 0.1Hz,  

Max:

 20.0Hz  

 

Figure-81

Figure-82

    Pr.51: Frequency Auto Reset Enable/Disable:

 

If auto reset enable and system into 

error, if all frequency are over/below the protect value as hysteresis value ,relay output 

switches on at the end of the Reset time. If Auto reset is disable, after all frequency are 

over/below hysteresis value, relay output switches manually. (Using ESC button).

Default:

 Disable,  

Min:

 Disable,  

Max:

 Enable

Summary of Contents for EM-07

Page 1: ...es of V1 V2 V3 V12 V23 V31 F1 F2 F3 It shows the minimum maximum average and demand values of I1 I2 I3 S1 S2 S3 High Low voltage current frequency adjustable Phase Neutral or Phase Phase protection ad...

Page 2: ...ase current and 3 phase voltage and neutral N L1 L2 L3 Load A1 A2 85 240VAC 50 60Hz 6VA B GND A RS485 COM NC OUT 5A 250VAC NO k3 k2 k1 Curent Transformer Connections l3 l2 l1 CT1 P1 S1 P2 S2 CT2 P1 S1...

Page 3: ...gether with the device Place the switch or circuit breaker close to the device or in a location that is easily accessible for the operator Be sure that the panel to which the device is mounted does no...

Page 4: ...surement values to another min max avg dmd State of Menu To navigate from menu parameters to another State of changing parameter Decrease value of parameter 7 Definition of Buttons 1 It shows phase nu...

Page 5: ...when you press the Down button Figure 3 It shows the phase neutral voltage values The figure 4 is displayed when you press the Down button Figure 4 It shows the phase neutral minimum voltage values T...

Page 6: ...shows the mean apparent power values of each phase The figure 20 is displayed when you press the Down button Figure 20 It shows the apparent power demand values of each phase The figure 21 is displaye...

Page 7: ...l number and version number You can use ESC button for exit menu Figure 25 Figure 26 12 Settings Figure 29 Set The Home screen is displayed when the device is energized When you press the up button to...

Page 8: ...19 Voltage Protection Type Figure 33 Figure 32 Set Esc V Figure 42 Figure 43 Figure 34 Figure 35 Figure 36 Figure 37 Figure 38 Figure 39 V V Figure 40 V Figure 41 Press Menu button and enter password...

Page 9: ...e Determines delay close time If all voltage below the high voltage protect value as a hysteresis voltage relay output switches close at the end of the reset time Default 3sec Min 1sec Max 10000sec Pr...

Page 10: ...medium voltage you can use VTR Default 1 Min 1 Max 999 Pr 13 Voltage Asymmetry Protection Reset Time Determines delay close time If calculated asymmetry value over the voltage asymmetry protect value...

Page 11: ...Reset Enable Disable Pr 36 Current Transformer Ratio Pr 37 Current Fuses Enable Disable Pr 38 Demurrage Protection Enable Disable Pr 39 Demurrage Protection Time Pr 40 Demurrage Protection Factor Set...

Page 12: ...ut switches close at the end of the reset time Default 10sec Min 1sec Max 10000sec Pr 27 Low Current Protection Reset Time Determines delay close time If all current below the low current protect valu...

Page 13: ...c Min 1sec Max 10000sec Pr 33 Current Asymmetry Protection Hysteresis Required hysteresis current for current asymmetry warning is programmed Default 3 Min 1 Max 20 Pr 34 Current Asymmetry Protection...

Page 14: ...hen you press the up button You enter Frequency set when you press Menu button If you enter Frequency set menu the figure 72 Pr 41 displayed This menu have 11 different current set value When you pres...

Page 15: ...Disable Max Enable Pr 46 Low Frequency Protection Value Determines the minimum operating frequency value of load Default 49Hz Min 45 0Hz Max 70 0Hz Pr 47 Low Frequency Protection Delay Time Determine...

Page 16: ...d to enter program list The figure 26 Voltage SET is displayed when you enter password and press the Menu button The figure 27 Current SET is displayed when you press the up button The figure 28 Frequ...

Page 17: ...ty Default 1 Min 1 Max 20 Pr 58 Demand Record Delete You can delete demand and average records If cut off device energy min max average and demand values are deleted Figure 87 Figure 88 Figure 89 Figu...

Page 18: ...ton until you see the General SET Step 2 Pr 54 is displayed when you press the SET button and press Up button You will see Pr 55 It is using for enable disable password protection It is deleted from s...

Page 19: ...displayed when you press the SET button It is using for setting high current protection value It is deleted from screen when you press the SET button Step 3 You can increase decrease value to use Up D...

Page 20: ...see the General SET Step 2 Pr 54 is displayed when you press the SET button and press Up button You will see Pr 57 It is using for setting demand time It is deleted from screen when you press the SET...

Page 21: ...you press the SET button You can increase decrease value to use Up Down Button You can use SET button to save The figure 40 is displayed when you press the SET button Press Up button until you see th...

Page 22: ...ecrease value to use Up Down Button You can use SET button to save The figure 56 is displayed when you press the SET button Press Up button until you see the Pr 20 figure 51 A A Figure 56 Pr 40 is usi...

Page 23: ...Pr 16 Pr 11 Pr 2 Pr 21 Pr 26 Pr 42 Pr 47 Pr 31 Pr 39 Pr 40 Pr 7 Pr 12 Pr 3 Pr 22 Pr 27 Pr 43 Pr 48 Pr 32 Pr 8 Pr 13 Pr 17 Pr 18 Pr 19 High Voltage Value High Current Value Low Current Value High Freq...

Page 24: ...www tense com tr 23 23 23 23 22 20 19 19 19 18 18 18 17 17 17 16 16 15 15 13 10 7 6 6 4 4 4 3 3 2 2 2 2 1 1 Connections Diagrams 26 Dimensions 28 Index 27 Technicial Specifications 29 Contact 25 Param...

Reviews: