background image

1 - Connection Diagrams:

-1-

2 - Points to take into consideration in the selection and connection of Current Transformer:

In order to prevent any mistake while connecting the output terminals of the current transformer, 

use cables in different colors for each phase or designate a number for each cable.

Keep the cables connected to the output terminals of the current transformer away from the 

high-voltage line.

In order to prevent any shake on the current transformer, fix it on the bus-bar, cable or rail.

Be sure that the current transformer value is higher than the maximum current drawn from the 

system.

3 - Warnings:

Do not expose the LCD display directly to sunlight in order to avoid any harm on it.
Note that the temperature level on the panel to which the device is mounted is at the range of 

operating temperature of the device (-20°C.....55°C)
There must be a space of 5cm behind the device after its installation.

Use the device according to the instructions specified by us.

Fix the device securely to the front-cover of the panel with the apparatus delivered together with the 

device.

Place the switch or circuit breaker close to the device or in a location that is easily accessible for the 
operator.

Be sure that the panel to which the device is mounted does not operate in a humid environment.

Place a switch or circuit breaker on the system during installation of the device.
 Please note that the cables must not be energized during installation.
Flexible monitored and twisted cables must be used for the input and output lines which are not 

connected to the mains.
The technical personnel according with the instructions specified in the user's manual must perform 

installation of the device and electrical connections.
The feeder cables must be compatible with the requirements of IEC 60227 or IEC 60245

5 - General:

 

    

EM-07 Multimeter measures the load on the system and voltage, current, apparent power minimum and 

maximum values, demands related to this load on the system.

4 - Maintenance of the Device:

    

De-energize and disconnect the device. Clean the body of the device with a dry or damp-dry cloth. Do not 

use conductive or other chemical substances as a cleaning agent that can damage the device. After 

cleaning the device, make its connections and check whether it is working by energizing it.

-2-

Figure-1:

 3P4W connection type: 3 phase current and 3 phase voltage and neutral. 

N

L1

L2
L3

Load

A1

A2

85-240VAC

50/60Hz. 

<

6VA

B

GND

A

RS485

COM

NC

OUT

5A/250VAC

NO

k3

k2

k1

Curent Transformer Connections

l3

l2

l1

CT1

P1

S1

P2

S2

CT2

P1

S1

P2

S2

CT3

P1

S1

P2

S2

N

Voltage Inputs

L1

L2

L3

Figure-1

Summary of Contents for EM-07

Page 1: ...es of V1 V2 V3 V12 V23 V31 F1 F2 F3 It shows the minimum maximum average and demand values of I1 I2 I3 S1 S2 S3 High Low voltage current frequency adjustable Phase Neutral or Phase Phase protection ad...

Page 2: ...ase current and 3 phase voltage and neutral N L1 L2 L3 Load A1 A2 85 240VAC 50 60Hz 6VA B GND A RS485 COM NC OUT 5A 250VAC NO k3 k2 k1 Curent Transformer Connections l3 l2 l1 CT1 P1 S1 P2 S2 CT2 P1 S1...

Page 3: ...gether with the device Place the switch or circuit breaker close to the device or in a location that is easily accessible for the operator Be sure that the panel to which the device is mounted does no...

Page 4: ...surement values to another min max avg dmd State of Menu To navigate from menu parameters to another State of changing parameter Decrease value of parameter 7 Definition of Buttons 1 It shows phase nu...

Page 5: ...when you press the Down button Figure 3 It shows the phase neutral voltage values The figure 4 is displayed when you press the Down button Figure 4 It shows the phase neutral minimum voltage values T...

Page 6: ...shows the mean apparent power values of each phase The figure 20 is displayed when you press the Down button Figure 20 It shows the apparent power demand values of each phase The figure 21 is displaye...

Page 7: ...l number and version number You can use ESC button for exit menu Figure 25 Figure 26 12 Settings Figure 29 Set The Home screen is displayed when the device is energized When you press the up button to...

Page 8: ...19 Voltage Protection Type Figure 33 Figure 32 Set Esc V Figure 42 Figure 43 Figure 34 Figure 35 Figure 36 Figure 37 Figure 38 Figure 39 V V Figure 40 V Figure 41 Press Menu button and enter password...

Page 9: ...e Determines delay close time If all voltage below the high voltage protect value as a hysteresis voltage relay output switches close at the end of the reset time Default 3sec Min 1sec Max 10000sec Pr...

Page 10: ...medium voltage you can use VTR Default 1 Min 1 Max 999 Pr 13 Voltage Asymmetry Protection Reset Time Determines delay close time If calculated asymmetry value over the voltage asymmetry protect value...

Page 11: ...Reset Enable Disable Pr 36 Current Transformer Ratio Pr 37 Current Fuses Enable Disable Pr 38 Demurrage Protection Enable Disable Pr 39 Demurrage Protection Time Pr 40 Demurrage Protection Factor Set...

Page 12: ...ut switches close at the end of the reset time Default 10sec Min 1sec Max 10000sec Pr 27 Low Current Protection Reset Time Determines delay close time If all current below the low current protect valu...

Page 13: ...c Min 1sec Max 10000sec Pr 33 Current Asymmetry Protection Hysteresis Required hysteresis current for current asymmetry warning is programmed Default 3 Min 1 Max 20 Pr 34 Current Asymmetry Protection...

Page 14: ...hen you press the up button You enter Frequency set when you press Menu button If you enter Frequency set menu the figure 72 Pr 41 displayed This menu have 11 different current set value When you pres...

Page 15: ...Disable Max Enable Pr 46 Low Frequency Protection Value Determines the minimum operating frequency value of load Default 49Hz Min 45 0Hz Max 70 0Hz Pr 47 Low Frequency Protection Delay Time Determine...

Page 16: ...d to enter program list The figure 26 Voltage SET is displayed when you enter password and press the Menu button The figure 27 Current SET is displayed when you press the up button The figure 28 Frequ...

Page 17: ...ty Default 1 Min 1 Max 20 Pr 58 Demand Record Delete You can delete demand and average records If cut off device energy min max average and demand values are deleted Figure 87 Figure 88 Figure 89 Figu...

Page 18: ...ton until you see the General SET Step 2 Pr 54 is displayed when you press the SET button and press Up button You will see Pr 55 It is using for enable disable password protection It is deleted from s...

Page 19: ...displayed when you press the SET button It is using for setting high current protection value It is deleted from screen when you press the SET button Step 3 You can increase decrease value to use Up D...

Page 20: ...see the General SET Step 2 Pr 54 is displayed when you press the SET button and press Up button You will see Pr 57 It is using for setting demand time It is deleted from screen when you press the SET...

Page 21: ...you press the SET button You can increase decrease value to use Up Down Button You can use SET button to save The figure 40 is displayed when you press the SET button Press Up button until you see th...

Page 22: ...ecrease value to use Up Down Button You can use SET button to save The figure 56 is displayed when you press the SET button Press Up button until you see the Pr 20 figure 51 A A Figure 56 Pr 40 is usi...

Page 23: ...Pr 16 Pr 11 Pr 2 Pr 21 Pr 26 Pr 42 Pr 47 Pr 31 Pr 39 Pr 40 Pr 7 Pr 12 Pr 3 Pr 22 Pr 27 Pr 43 Pr 48 Pr 32 Pr 8 Pr 13 Pr 17 Pr 18 Pr 19 High Voltage Value High Current Value Low Current Value High Freq...

Page 24: ...www tense com tr 23 23 23 23 22 20 19 19 19 18 18 18 17 17 17 16 16 15 15 13 10 7 6 6 4 4 4 3 3 2 2 2 2 1 1 Connections Diagrams 26 Dimensions 28 Index 27 Technicial Specifications 29 Contact 25 Param...

Reviews: