background image

3

78570

INSTALLER: Please leave these instructions with the
owner.
OWNER:  Please retain these instructions for future
reference.

Important Information

WARNING: Any change to this heater or its con-
trols can be dangerous.

IMPORTANT: READ THESE INSTRUCTIONS CARE-
FULLY BEFORE INSTALLING.

WARNING: Do not allow fans to blow directly into
the fireplace.  Avoid any drafts that alter burner
flame patterns.

WARNING: Do not use a blower insert, heat exchanger
insert or other accessory not approved for use with this
heater.

WARNING:  This appliance is for installation only
in a solid-fuel burning masonry or UL 127 factory-
built fireplace or in a listed ventless firebox enclo-
sure.  It has been designed certified for these
installations.  Exception:  DO NOT install this
appliance in a factory-built fireplace that includes
instructions stating it has not been tested or
should not be used with unvented gas logs.

NOTES

Due to high temperatures, the appliance should be

located out of traffic and away from furniture and draper-
ies.

Installation and repair should be done by an experienced

and qualified service person or gas appliance installer.

The appliance must be inspected before use and at least

annually by a professional service person. More frequent
cleaning may be required due to excessive lint from
carpeting, bedding material, dust and pet hair, etc. It is
important that the control compartment, burners and
circulating air passageways of the appliance be kept clean.
Refer to instructions on Page 14.

DO NOT place clothing or other flammable material on or

near the appliance.

This appliance must only be used with pressures at the inlet

as shown in Table 1, page 9.  Failure to check and document
these pressures may void the warranty.

The installation must conform with local codes or, in the

absence of local codes, with the NATIONAL FUEL GAS CODE,
ANSI Z223, latest edition.  If you cannot reference these codes,
DO NOT attempt to install this unit.

Any safety screen or guard removed for servicing an

appliance must be replaced prior to operating the heater.

The appliance and its appliance main gas valve must be

disconnected from the gas supply piping system during any
pressure testing of that system at test pressures in excess of
1/2 psig (3.5 kpa).

The appliance must be isolated from the gas supply piping

system by closing its equipment shut-off valve during any
testing of the gas supply piping system at test pressures equal
to or less than 1/2 psig (3.5kpa).

DO NOT use this heater in recreational vehicles, bedrooms or

bathrooms.

If this is the ONLY gas appliance, we recommend a

minimum 200 pound cylinder with a fill gauge.  Use of a 100
pound cylinder is not recommended.  Other household gas
appliances may require the tank size to be larger.  Do not
operate the vent-free heater if the fuel level in the propane
tank is below 1/4 full.

DO NOT use this heater if any part of it has been submerged

under water. Immediately call a qualified technician to inspect
the appliance and replace any part of the control system and
any gas control which has been under water.

Any outside air ducts in the fireplace shall be permanently

closed at the time of appliance installation.

Check local, state or city codes to determine if unvented

heaters are permitted.  If unvented heaters are not permit-
ted, the fireplace chimney damper must be fixed at a

minimum free (vent) opening area of 15 sq. ins.  This must
be accomplished by a clamp or screw on the chimney
damper to stop at the minimum vent area.  The fireplace
must also have a minimum free (vent) opening of 15 sq.
ins. (Fig. 1)

This appliance may be installed in an after-market* manufac-

tured "mobile" home where not prohibited by state or local
codes.
*After-market:  Completion of sale, not for purpose of re-sale
from the manufacturer.

OUTSIDE AIR DAMPER OR ASH DUMP (IF PRESENT)

MUST BE CLOSED AND SEALED.

Young children should be carefully supervised when they

are in the same room as the appliance.

WARNING:  During manufacturing, fabricating and
shipping, various components of this appliance are
treated with certain oils, films or bonding agents.  These
chemicals are not harmful but may produce annoying
smoke and smells as they are burned off during the
initial operation of the appliance, possibly causing
headaches and eye/lung irritation.  This is a normal and
temporary occurrence.

Input (BTU/hr)

BTU/hr

Model

Fuel

Hi

Lo

VFL34RN

Natural

34,000

22,000

VFL34RP

LP/Propane

34,000

25,500

An unvented room heater having an input rating of more

than 10,000 btu per hour shall not be installed in a bedroom
or a bathroom.

For Installation of High Altitude

When installing this fireplace at an elevation above 2,000 feet
(in the United States), it may be necessary to decrease the
input rating by changing the existing burner orifice to a smaller
size.  Input should be reduced four percent (4%) for each 1,000
feet above sea level, unless the heating value of the gas has
been reduced, in which case this general rule will not apply.  To
identify the proper orifice size, check with the local gas utility.

Consult your local gas utility for assistance in determining the
proper orifice for your location.

Summary of Contents for VFL34MN

Page 1: ...es air oxygen from the room in which it is installed Provisions for adequate combustion and ventilation air must be provided Refer to Section Provisions For Adequate Combustion and Ventilation Air Page 4 FOR YOUR SAFETY Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do n...

Page 2: ...ighting 13 Flame Check 13 Managing Heat Output 14 Maintenance Cleaning 14 Troubleshooting 15 Servicing 15 Repair Parts 16 Warranty Information 17 Installation and Startup Checklist 18 Warranty Registration 20 Table of Contents Minimum Dimensions for Existing Solid Fuel Burning Fireplaces This appliance may be installed in an aftermarket permanently located manufactured mobile home where not prohib...

Page 3: ...DO NOT use this heater in recreational vehicles bedrooms or bathrooms If this is the ONLY gas appliance we recommend a minimum 200 pound cylinder with a fill gauge Use of a 100 pound cylinder is not recommended Other household gas appliances may require the tank size to be larger Do not operate the vent free heater if the fuel level in the propane tank is below 1 4 full DO NOT use this heater if a...

Page 4: ...e Example Space size 25 length x 25 width x 8 ceiling height 5 000 cu ft volume of space If additional ventilation from adjoining room s is supplied with grills or doorless openings add the volume of these rooms to compute the total volume of the applicable space 2 Divide the space volume by 50 cubic feet to determine the maximum BTU Hr the space can support ________ volume of space 50 cu ft Maxim...

Page 5: ...onal Fuel Gas Code NFPA 54 ANSI Z223 1 Section 5 3 Air for Combustion and Ventilation for required size of ventilation grills or ducts IMPORTANT Do not provide openings for inlet or outlet air into attic if attic has a thermostat controlled power vent Heated air entering the attic will activate the power vent L W D Flue Damper Closed for Unvented Operation and Maximum Heat Output Flue Damper Locke...

Page 6: ... do so could cause gas leaks Holes are provided in the sheet metal chassis Fig 3 and should be used for securing the log set After locating the chassis correctly in the fireplace mark the hole positions on the fireplace floor Drill two 1 8 diameter holes approximately 1 2 deep Use the two screws to secure the chassis to the fireplace floor Fig 3 Clearances NOTE The following instructions regarding...

Page 7: ...ol valve gas line inlet The inlet to these units is 1 2 NPT If installation is for L P gas have L P installer use two stage regulation and make all connections from storage tank to heater Refer to the National Fuel Gas Code for the proper supply tank size with the Btu s Hr requirements If this is the ONLY gas appliance we recommend a minimum 200 pound cylinder with a fill gauge Use of a 100 pound ...

Page 8: ... for specific requirements Piped Gas Supply Drop Manual Shut Off Valve Horizontal Ground Joint Union Tee Fitting Nipple 3 Min Cap 1 8 N P T Plugged Hole for Test Gauge Gas Valve Drop Manual Shut Off Valve Ground Joint Union Tee Fitting Nipple 3 Min Cap 1 8 N P T Plugged Hole for Test Gauge Gas Valve Tubing Gas Supply Riser Manual Shut Off Valve Ground Joint Union Tee Fitting Nipple 3 Min Cap 1 8 N...

Page 9: ... 7 0 w c 11 0 w c Min 5 0 w c 10 8 w c Regulator Pressure 3 5 w c 10 0 w c Minimum inlet supply pressure for the purpose of input adjustment Gas Pressure Check The gas inlet pressure specified in Table 1 is the pressure where the field installed gas line connects to the gas control This is measured at the inlet test port on the gas valve in the appliance Ensure that pressure is as shown in Table 1...

Page 10: ...c ash on burner pilot or logs 6 Platinum embers are to be placed only on top of the front burner port area Equally space emblers one layer thick Do not pile ember material over one layer thick as this does not enhance the ember appearance or improve the log set performance Fig 8 7 Flames must not impinge touch on logs WARNING Do not use more embers than those supplied with your unit Do not use emb...

Page 11: ... connecting a wall switch thermostat or remote control use only the top and bottom control valve terminals for attachment of the wire leads do not use center terminal of terminal block Figs 9 and 10 Remote Control Information The remote receiver does not need to be secured to the VFL34R N P base but can be placed along side of the log base assembly larger fireboxes only in a wall mounted switch bo...

Page 12: ...en smell for gas including near the floor If you smell gas STOP Follow B in the safety information above If you don t smell gas go to the next step 4 Refer to Figure 13 Locate the pilot It is positioned on the burner behind the front log and below the right twig times This will cause a spark at the pilot which will ignite the pilot gas 7 Hold the control knob for 20 seconds to prevent the flame fa...

Page 13: ...pliance is operating WARNING The glowing ember base and all the logs are manufactured from bonded ceramic fiber This is a commonly used material in industry worldwide In the event of the logs and base being removed care should be taken not to damage the bonded material Intentional misuse of or deliberately fragmenting the material could lead to inhaling fibers and be injurious to health Insure the...

Page 14: ...e required under normal use Dusting the front grate or the control knob panel may be required occasionally Do not use any cleaning fluids to clean the logs or any other part of the appliance If the flames show any unusual shapes or behavior or if the burner s fail to ignite properly then the burner holes may require cleaning If this occurs contact your nearest dealer to get the appliance serviced ...

Page 15: ...lace assembly Ignitor cable pinched or broken Free ignitor cable if damaged replace it Ignitor cable not connected to ignitor Connect cable to ignitor 2 Pilot will not stay lit Partially clogged ODS pilot orifice Contact qualified service person or your gas company Corrosion of thermocouple contact Clean thermocouple contact Bad gas valve Replace gas valve Control knob not pressed in long After pi...

Page 16: ...78439 1 Air Scoop 78445 78445 1 Valve Natural 55463 1 Valve LP Propane 55462 1 Burner Natural 78474 1 Burner LP Propane 78473 1 Pilot Natural OP 78167 1 Pilot LP Propane OP 78169 1 Manifold Tube Split Nut 78456 78456 1 Orifice 31 Natural 78458 1 Orifice 50 LP Propane 78451 1 Tube Flexible Gas Inlet 71598 71598 1 Tube Pilot 3 16 78583 78583 1 Ignitor w Nut Piezo 65180 65180 1 Wire Assembly Rocker S...

Page 17: ...allation instructions and in compliance with local codes and ordinances The logs must be placed strictly in accor dance with the arrangement described in the installation instructions The Product must be operated and maintained according to the instructions furnished Alteration of the Product in any way is prohibited and voids any and all war ranties Removal of the data plate alters the Products a...

Page 18: ...rners as well as proper appearance of flames Verify that ceramic fiber and refractory components are properly positioned and secure Rear burner must not contact logs Verify adequate clearance to mantels and other combustibles Demonstrate correct operation of the product to the consumer NOTE LP models must not be operated if fuel tank is less than 1 4 full Observe the consumer operating the product...

Page 19: ...burners as well as proper appearance of flames Verify that ceramic fiber and refractory components are properly positioned and secure Rear burner must not contact logs Verify adequate clearance to mantels and other combustibles Demonstrate correct operation of the product to the consumer NOTE LP models must not be operated if fuel tank is less than 1 4 full Observe the consumer operating the produ...

Page 20: ...er your warranty please provide the information indicated on this form and mail it to TEMCO Fireplace Products Attn Warranty Registration 410 Admiral Blvd Mississauga Ontario Canada L5T 2N6 Model ______________________________________ I certify that I have followed all codes and regulations and adhered to the TEMCO installation instructions I have completed the proper installation and startup chec...

Reviews: