background image

14

78570

Managing Heat Output

The heat output from the appliance can be controlled by the
position of the flue damper on vented fireplaces.

The damper setting should be fully closed for maximum heat
output, partially closed for less heat output and fully open for
minimum heat output.

The appliance may be used in a working solid fuel burning
fireplace with the fuel damper closed only if unvented appli-
ances are permitted by local state and city codes.  It may also
be operated as a decorative appliance whose prime function
lies in the aesthetic effect of the flames when installed in a solid
fuel burning fireplace with the flue damper open.  If unvented
heaters are not permitted, the fireplace vent damper must be
locked at a minimum free (vent) area of 15 sq. ins.

Whenever the appliance is operated with the fireplace's
flue damper closed, glass doors - if present - must be open
and the outside air damper and the ash dump (if the
fireplace is equipped with either one) must be closed.

The heat output from the appliance when operated as a vent-
free heater may be controlled by adjusting the main gas valve.
Reference lighting instructions on Page 11 and chart on Page 3
which shows inputs at all settings.

The main gas valve may be adjusted anywhere between high
and low to give the desired combination of flame aesthetics and
heat output.

Maintenance

Cleaning

CAUTION:  Before cleaning or moving logs or other parts of the
unit, be sure to read the section on important safeguards.

Cleaning should be done before the logs are used each year
and after long periods of non-use.  Professional servicing is
recommended.

All cleaning should be carried out when the appliance is cold.

Only limited cleaning will be required under normal use.
Dusting the front grate or the control knob panel may be
required occasionally.  Do not use any cleaning fluids to clean
the logs or any other part of the appliance.

If the flames show any unusual shapes or behavior, or if the
burner(s) fail to ignite properly, then the burner holes may
require cleaning.  If this occurs contact your nearest dealer to
get the appliance serviced.

Alternatively, the appliance can be cleaned by removing the
logs.  Handle the logs gently so as not to damage them.
Always lift each log by holding it carefully at each end.

After the logs are removed allowing access to the burner area,
use the brush attachment from your vacuum cleaner to carefully
remove dust and loose particles from the base, logs and from
around the burner.  Gloves are recommended when handling
the logs.  Use extreme caution when cleaning around the pilot
(ODS).  The pilot should not be moved or altered from the
original factory setting (Pilot to burner preset location).  To clean
the pilot, take an Air Duster can (computer cleaner compressed
air) and insert the nozzle into the primary air inlet.  Shoot a
short blast of air into the inlet to clear dust. (Fig. 20)  The burner
should not be removed or taken out of it’s locked and secure
position (proper location of burners are critical).

Logs must be carefully replaced in their orignial, preset posi-
tions, as shown in Figure 21, to prevent the rear flames from
touching any log.  No other arrangement is permitted.  Incorrect
placement can diminish combustion efficiency and cause
sooting.

A qualified gas professional should periodically check and clean
the orifices and burners per National Fuel Gas Code, Appendix
B.

Lack of proper maintenance may void warranty.

Gas
Outlet

Primary Air
Inlet

T135

Fig. 20  Use a short burst of air into the primary air inlet to clean
pilot.

Fig. 21  Correct log placement.

Rear Log

Right Twig

Left Twig

Front Log

TL106

Summary of Contents for VFL34MN

Page 1: ...es air oxygen from the room in which it is installed Provisions for adequate combustion and ventilation air must be provided Refer to Section Provisions For Adequate Combustion and Ventilation Air Page 4 FOR YOUR SAFETY Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do n...

Page 2: ...ighting 13 Flame Check 13 Managing Heat Output 14 Maintenance Cleaning 14 Troubleshooting 15 Servicing 15 Repair Parts 16 Warranty Information 17 Installation and Startup Checklist 18 Warranty Registration 20 Table of Contents Minimum Dimensions for Existing Solid Fuel Burning Fireplaces This appliance may be installed in an aftermarket permanently located manufactured mobile home where not prohib...

Page 3: ...DO NOT use this heater in recreational vehicles bedrooms or bathrooms If this is the ONLY gas appliance we recommend a minimum 200 pound cylinder with a fill gauge Use of a 100 pound cylinder is not recommended Other household gas appliances may require the tank size to be larger Do not operate the vent free heater if the fuel level in the propane tank is below 1 4 full DO NOT use this heater if a...

Page 4: ...e Example Space size 25 length x 25 width x 8 ceiling height 5 000 cu ft volume of space If additional ventilation from adjoining room s is supplied with grills or doorless openings add the volume of these rooms to compute the total volume of the applicable space 2 Divide the space volume by 50 cubic feet to determine the maximum BTU Hr the space can support ________ volume of space 50 cu ft Maxim...

Page 5: ...onal Fuel Gas Code NFPA 54 ANSI Z223 1 Section 5 3 Air for Combustion and Ventilation for required size of ventilation grills or ducts IMPORTANT Do not provide openings for inlet or outlet air into attic if attic has a thermostat controlled power vent Heated air entering the attic will activate the power vent L W D Flue Damper Closed for Unvented Operation and Maximum Heat Output Flue Damper Locke...

Page 6: ... do so could cause gas leaks Holes are provided in the sheet metal chassis Fig 3 and should be used for securing the log set After locating the chassis correctly in the fireplace mark the hole positions on the fireplace floor Drill two 1 8 diameter holes approximately 1 2 deep Use the two screws to secure the chassis to the fireplace floor Fig 3 Clearances NOTE The following instructions regarding...

Page 7: ...ol valve gas line inlet The inlet to these units is 1 2 NPT If installation is for L P gas have L P installer use two stage regulation and make all connections from storage tank to heater Refer to the National Fuel Gas Code for the proper supply tank size with the Btu s Hr requirements If this is the ONLY gas appliance we recommend a minimum 200 pound cylinder with a fill gauge Use of a 100 pound ...

Page 8: ... for specific requirements Piped Gas Supply Drop Manual Shut Off Valve Horizontal Ground Joint Union Tee Fitting Nipple 3 Min Cap 1 8 N P T Plugged Hole for Test Gauge Gas Valve Drop Manual Shut Off Valve Ground Joint Union Tee Fitting Nipple 3 Min Cap 1 8 N P T Plugged Hole for Test Gauge Gas Valve Tubing Gas Supply Riser Manual Shut Off Valve Ground Joint Union Tee Fitting Nipple 3 Min Cap 1 8 N...

Page 9: ... 7 0 w c 11 0 w c Min 5 0 w c 10 8 w c Regulator Pressure 3 5 w c 10 0 w c Minimum inlet supply pressure for the purpose of input adjustment Gas Pressure Check The gas inlet pressure specified in Table 1 is the pressure where the field installed gas line connects to the gas control This is measured at the inlet test port on the gas valve in the appliance Ensure that pressure is as shown in Table 1...

Page 10: ...c ash on burner pilot or logs 6 Platinum embers are to be placed only on top of the front burner port area Equally space emblers one layer thick Do not pile ember material over one layer thick as this does not enhance the ember appearance or improve the log set performance Fig 8 7 Flames must not impinge touch on logs WARNING Do not use more embers than those supplied with your unit Do not use emb...

Page 11: ... connecting a wall switch thermostat or remote control use only the top and bottom control valve terminals for attachment of the wire leads do not use center terminal of terminal block Figs 9 and 10 Remote Control Information The remote receiver does not need to be secured to the VFL34R N P base but can be placed along side of the log base assembly larger fireboxes only in a wall mounted switch bo...

Page 12: ...en smell for gas including near the floor If you smell gas STOP Follow B in the safety information above If you don t smell gas go to the next step 4 Refer to Figure 13 Locate the pilot It is positioned on the burner behind the front log and below the right twig times This will cause a spark at the pilot which will ignite the pilot gas 7 Hold the control knob for 20 seconds to prevent the flame fa...

Page 13: ...pliance is operating WARNING The glowing ember base and all the logs are manufactured from bonded ceramic fiber This is a commonly used material in industry worldwide In the event of the logs and base being removed care should be taken not to damage the bonded material Intentional misuse of or deliberately fragmenting the material could lead to inhaling fibers and be injurious to health Insure the...

Page 14: ...e required under normal use Dusting the front grate or the control knob panel may be required occasionally Do not use any cleaning fluids to clean the logs or any other part of the appliance If the flames show any unusual shapes or behavior or if the burner s fail to ignite properly then the burner holes may require cleaning If this occurs contact your nearest dealer to get the appliance serviced ...

Page 15: ...lace assembly Ignitor cable pinched or broken Free ignitor cable if damaged replace it Ignitor cable not connected to ignitor Connect cable to ignitor 2 Pilot will not stay lit Partially clogged ODS pilot orifice Contact qualified service person or your gas company Corrosion of thermocouple contact Clean thermocouple contact Bad gas valve Replace gas valve Control knob not pressed in long After pi...

Page 16: ...78439 1 Air Scoop 78445 78445 1 Valve Natural 55463 1 Valve LP Propane 55462 1 Burner Natural 78474 1 Burner LP Propane 78473 1 Pilot Natural OP 78167 1 Pilot LP Propane OP 78169 1 Manifold Tube Split Nut 78456 78456 1 Orifice 31 Natural 78458 1 Orifice 50 LP Propane 78451 1 Tube Flexible Gas Inlet 71598 71598 1 Tube Pilot 3 16 78583 78583 1 Ignitor w Nut Piezo 65180 65180 1 Wire Assembly Rocker S...

Page 17: ...allation instructions and in compliance with local codes and ordinances The logs must be placed strictly in accor dance with the arrangement described in the installation instructions The Product must be operated and maintained according to the instructions furnished Alteration of the Product in any way is prohibited and voids any and all war ranties Removal of the data plate alters the Products a...

Page 18: ...rners as well as proper appearance of flames Verify that ceramic fiber and refractory components are properly positioned and secure Rear burner must not contact logs Verify adequate clearance to mantels and other combustibles Demonstrate correct operation of the product to the consumer NOTE LP models must not be operated if fuel tank is less than 1 4 full Observe the consumer operating the product...

Page 19: ...burners as well as proper appearance of flames Verify that ceramic fiber and refractory components are properly positioned and secure Rear burner must not contact logs Verify adequate clearance to mantels and other combustibles Demonstrate correct operation of the product to the consumer NOTE LP models must not be operated if fuel tank is less than 1 4 full Observe the consumer operating the produ...

Page 20: ...er your warranty please provide the information indicated on this form and mail it to TEMCO Fireplace Products Attn Warranty Registration 410 Admiral Blvd Mississauga Ontario Canada L5T 2N6 Model ______________________________________ I certify that I have followed all codes and regulations and adhered to the TEMCO installation instructions I have completed the proper installation and startup chec...

Reviews: