4.7
Preparing the connection cables
4.7.1
Preparing the cable
The cable will be brought to the detection point. Professional standards for running wires and
maintaining and protecting cables must be followed.
4.7.2
Disconnecting power
If the central system to which the transmitter will be connected is already activated:
1.Block the system's alarms during the operation to avoid accidentally triggering them.
2.Disconnect power to the detector or the corresponding line.
4.7.3
Opening the detector
Remove the 4-mm hexagonal cover locking screw before unscrewing the detector's cover (Figure
2, 4).
4.7.4
Running the câble
Follow all instructions provided by the manufacturer of the cable gland and be sure
to properly connect the braided shield.
Figure 39: example of a double-compression cable gland to secure armored cable.
Sensor
Sealing ring
Cable shield grounding device
Armored cable
Sealing ring
Summary of Contents for OLCT 80 d
Page 1: ...NPO80GB Revision F 1 OLCT 80 GAS TRANSMITTER USER MANUAL...
Page 10: ...OLCT 80 GAS TRANSMITTER USER MANUAL 4 NPO80GB Revision F 1...
Page 56: ...OLCT 80 GAS TRANSMITTER USER MANUAL 50 NPO80GB Revision F 1...
Page 78: ...OLCT 80 GAS TRANSMITTER USER MANUAL 72 NPO80GB Revision F 1...
Page 80: ...OLCT 80 GAS TRANSMITTER USER MANUAL 74 NPO80GB Revision F 1...
Page 86: ...OLCT 80 GAS TRANSMITTER USER MANUAL 80 NPO80GB Revision F 1...
Page 93: ...OLCT 80 GAS TRANSMITTER USER MANUAL NPO80GB Revision F 1 87...
Page 94: ...OLCT 80 GAS TRANSMITTER USER MANUAL 88 NPO80GB Revision F 1...
Page 96: ...OLCT 80 GAS TRANSMITTER USER MANUAL 90 NPO80GB Revision F 1...
Page 104: ...OLCT 80 GAS TRANSMITTER USER MANUAL 98 NPO80GB Revision F 1...
Page 115: ...OLCT 80 GAS TRANSMITTER USER MANUAL NPO80GB Revision F 1 109...