![TELEDYNE OLDHAM SIMTRONICS Everywhereyoulook DG-TT7-S Operating Manual Download Page 27](http://html1.mh-extra.com/html/teledyne-oldham-simtronics/everywhereyoulook-dg-tt7-s/everywhereyoulook-dg-tt7-s_operating-manual_1081077027.webp)
MULTITOX DETECTOR
OPERATING MANUAL
NOSP17668
Revision 03
a
21
In this case, the output current is not isolated from power supply, consumed by the detector.
The 20mA current loop must be supplied with a PLC. The current return must be connected to the
0V at the level of the L- terminal. To proceed, please connect the 4 (V-) and 6 (L-) terminals at the
terminal block level of the device.
4.3.3.3
4-wires connection (isolated power)
When using a 4 wires connection, the current loop is provided by the input module or PLC. The
loop (L + and L-) is optically isolated from the detector. 4-20mA or 0-22mA input module of the
PLC must power up the current loop with, at least 8V at the terminal level.
4.3.4
Relay (option)
An optional card with 3 relays can be added on the detector.
The output relays can be connected to the detection unit or warning devices.
For the network version, the optional relay card cannot be installed.
Each relay can be configured:
•
normally closed or normally open.
•
on one or more states of the detector (fault, permanent Inhibition, alarms).
Relays configured at factory setting : refer to § 6.8.6.1Erreur ! Source du renvoi introuvable.
Summary of Contents for Everywhereyoulook DG-TT7-S
Page 32: ...MULTITOX DETECTOR OPERATING MANUAL 26 NOSP17668 Revision 03a ...
Page 34: ...MULTITOX DETECTOR OPERATING MANUAL 28 NOSP17668 Revision 03a ...
Page 47: ...MULTITOX DETECTOR OPERATING MANUAL NOSP17668 Revision 03a 41 ...
Page 54: ...MULTITOX DETECTOR OPERATING MANUAL 48 NOSP17668 Revision 03a ...
Page 58: ...MULTITOX DETECTOR OPERATING MANUAL 52 NOSP17668 Revision 03a ...
Page 60: ...MULTITOX DETECTOR OPERATING MANUAL 54 NOSP17668 Revision 03a ...
Page 69: ...MULTITOX DETECTOR OPERATING MANUAL NOSP17668 Revision 03a 63 10 Declaration of conformity ...
Page 70: ...MULTITOX DETECTOR OPERATING MANUAL 64 NOSP17668 Revision 03a ...
Page 71: ...MULTITOX DETECTOR OPERATING MANUAL NOSP17668 Revision 03a 65 ...