![TELEDYNE OLDHAM SIMTRONICS Everywhereyoulook DG-TT7-S Operating Manual Download Page 25](http://html1.mh-extra.com/html/teledyne-oldham-simtronics/everywhereyoulook-dg-tt7-s/everywhereyoulook-dg-tt7-s_operating-manual_1081077025.webp)
MULTITOX DETECTOR
OPERATING MANUAL
NOSP17668
Revision 03
a
19
4.3.1
Connection of the electrical ground braid
Use a shield connection clamp (not supplied) to connect the shielding of the cable to the electric
ground of the housing (see § below).
4.3.2
Grounding
A M4 screw passes through the body of the enclosure, enabling the electronic ground of the
housing to be connected to the local ground.
It is recommended to use a yellow / green wire with a ring lug (section ≥ others wires and ≥1.5
mm²). The armour of the power cable is normally connected to the ground of the detector, but it
may depend on site practices.
4.3.3
Connection
There are three different type of power supply:
•
3-wires connection (source):
-
The output current is not isolated from power supply, provided from detector
(standard connection).
•
3-wires connection (sink):
-
The output current is not isolated from power supply, consumed by the detector
•
4-wires connection:
-
The output current is isolated from power supply
NB :The power potentials are isolated fromthe electric ground of the housing.
Total loop resistance:
Whatever the power supply type (3 wires source ou sink, 4 wires), the total loop resistance
(re cable) should not exceed the following value:
mA
22
V
8
tage
supply vol
Power
maxi
R
−
=
The total loop resistance should not exceed 700
Ω
with a voltage of 24Vdc
Summary of Contents for Everywhereyoulook DG-TT7-S
Page 32: ...MULTITOX DETECTOR OPERATING MANUAL 26 NOSP17668 Revision 03a ...
Page 34: ...MULTITOX DETECTOR OPERATING MANUAL 28 NOSP17668 Revision 03a ...
Page 47: ...MULTITOX DETECTOR OPERATING MANUAL NOSP17668 Revision 03a 41 ...
Page 54: ...MULTITOX DETECTOR OPERATING MANUAL 48 NOSP17668 Revision 03a ...
Page 58: ...MULTITOX DETECTOR OPERATING MANUAL 52 NOSP17668 Revision 03a ...
Page 60: ...MULTITOX DETECTOR OPERATING MANUAL 54 NOSP17668 Revision 03a ...
Page 69: ...MULTITOX DETECTOR OPERATING MANUAL NOSP17668 Revision 03a 63 10 Declaration of conformity ...
Page 70: ...MULTITOX DETECTOR OPERATING MANUAL 64 NOSP17668 Revision 03a ...
Page 71: ...MULTITOX DETECTOR OPERATING MANUAL NOSP17668 Revision 03a 65 ...