![TELEDYNE OLDHAM SIMTRONICS Everywhereyoulook DG-TT7-S Operating Manual Download Page 18](http://html1.mh-extra.com/html/teledyne-oldham-simtronics/everywhereyoulook-dg-tt7-s/everywhereyoulook-dg-tt7-s_operating-manual_1081077018.webp)
MULTITOX DETECTOR
OPERATING MANUAL
12
NOSP17668
Revision 03
a
FUNCTIONAL SAFETY (DG-TT7-S)
SIL
SIL certified based on IEC/EN 61508 part 1 to 7 (2011) standards
Certification delivered by LCIE Bureau Véritas
•
The safety function is either integrating the 4/20 mA current loop, as an output, or the relays
one
•
PFD calculation is based on a 12 months verification frequency and a 24 hours MTTR, out of
the cell
CURRENT OUTPUT
Detecteur
Donnée
Definitions
Valeur
MultiTox
DG-TT7-S
λ
Failure rate per hour
7.35x10
-6
/h
SFF
Safety fraction failure (T1= 12 mois)
91.4 %
PFD
Probability of failure on Demande
2.80x10
-3
PFH
Probability of failure / h (1oo1)
6.34x10
-7
MTTR
Mean Time To Repair
Fault on cartridge
16 min
Fault on Detector
26 min
MTTR utilisé pour le calcul du PFD
300 min
SIL
compliance
HFT = 0 / G.Fixed / 30°C / type B
1
RELAY OUTPUT
Detecteur
Donnée
Definitions
Valeur
MultiTox
DG-TT7-S
λ
Failure rate per hour
7.18x10
-6
/h
SFF
Safety fraction failure (T1= 12 mois)
88.9 %
PFD
Probability of failure on Demande
3.50x10
-3
PFH
Probability of failure / h (1oo1)
7.94x10
-7
MTTR
Mean Time To Repair
Fault on cartridge
16 min
Fault on Detector
26 min
MTTR utilisé pour le calcul du PFD
300 min
SIL
compliance
HFT = 0 / G.Fixed / 30°C / type B
1
The above values are corresponding to electronic type C which has been certified with HW
Tyce C.
Updated SIL certificate for type D is pending (expected values will be at least equivalent to type
C)
Summary of Contents for Everywhereyoulook DG-TT7-S
Page 32: ...MULTITOX DETECTOR OPERATING MANUAL 26 NOSP17668 Revision 03a ...
Page 34: ...MULTITOX DETECTOR OPERATING MANUAL 28 NOSP17668 Revision 03a ...
Page 47: ...MULTITOX DETECTOR OPERATING MANUAL NOSP17668 Revision 03a 41 ...
Page 54: ...MULTITOX DETECTOR OPERATING MANUAL 48 NOSP17668 Revision 03a ...
Page 58: ...MULTITOX DETECTOR OPERATING MANUAL 52 NOSP17668 Revision 03a ...
Page 60: ...MULTITOX DETECTOR OPERATING MANUAL 54 NOSP17668 Revision 03a ...
Page 69: ...MULTITOX DETECTOR OPERATING MANUAL NOSP17668 Revision 03a 63 10 Declaration of conformity ...
Page 70: ...MULTITOX DETECTOR OPERATING MANUAL 64 NOSP17668 Revision 03a ...
Page 71: ...MULTITOX DETECTOR OPERATING MANUAL NOSP17668 Revision 03a 65 ...