4 Software Operation
MIX 56 User Manual
4-20
Telect, Inc. 122188-10 A0
Step
Action
1.
From the Directory screen, press
6
to select High Speed Configura-
tion, then Enter.
The High Speed Configuration screen appears.
2.
In the Name field, type a name for the DS3 circuit (up to 16 charac-
ters) and press Enter.
3.
Tab to the Clock Source field, select a clock source by pressing the
spacebar to toggle between DS3 Loop Timing and Internal, and
then press Enter.
◊
DS3 Loop Timing—Timing is recovered from the incoming
DS3 signal.
◊
Internal—Timing is generated by the onboard Stratum 4 clock.
NOTE
In DS3 networks, one network element provides master timing,
while the other one recovers timing from the incoming DS3 signal.
4.
Tab to the Mode field, select a DS3 mode by pressing the spacebar
to toggle between M13 and C-bit, and then press Enter.
MIX 56 by Telect MIX 56 Directory (Ctrl+D)
Help (?)
High Speed Configuration
------------------------
Name: High Speed
Clock Source: DS3 Loop Timing
Mode: M13
Optional C-bit LAPD Information
-------------------------------
Local Remote
--------------------------------- -------------------------------
Equipment ID:
Location ID:
Frame ID:
Unit ID:
Facility ID - Local:
Facility ID - Remote:
[Apply]