8. Follow the diagram below to connect two network elements.
Figure 5 - Connecting Two Network Elements
9. Install a backplane tracer lamp wire between the two repeaters and verify that both tracer
lamp LEDs light up.
10. Install designation strips and label them, using office standards.
11. Test circuits per office standards.
This procedure is complete.
Simplex Repeater
LBO Settings
CABLE
Repeater
to NE
distance
(feet)
FIGURE
Distance
Transmit
LBO
Setting
Repeater
to
Repeater
distance
(feet)
FIGURE
Distance
Receive
LBO
Setting
0-124
A or C
SHORT
0-124
B
SHORT
124-255
A or C
LONG
124-255
B
LONG
0-212
A or C
SHORT
0-212
B
SHORT
212-425
A or C
LONG
212-425
B
LONG
0-224
A or C
SHORT
0-224
B
SHORT
224-450
A or C
LONG
224-450
B
LONG
0-112
A or C
SHORT
0-112
B
SHORT
112-225
A or C
LONG
112-225
B
LONG
0-224
A or C
SHORT
0-224
B
SHORT
224-450
A or C
LONG
224-450
B
LONG
RG-59
720
728
734
735
NE
NE
TX
RX
TX
RX
SIMPLEX
REPEATER
710-3201-0002
A
B
Distance
Distance
O
I
I
IX
OX
O
O
I
O
I
OX
IX
SIMPLEX
REPEATER
710-3201-0002
Distance
C
Each network element can be located up to 900ft. from the far end repeaters IX port.