![Tekron TCG 01-G User Manual Download Page 24](http://html.mh-extra.com/html/tekron/tcg-01-g/tcg-01-g_user-manual_1077251024.webp)
TEK-TCG 01-G-Manual-v6-052021
P a g e
| 24
www.tekron.com
© 2021 by Tekron International Limited. All Rights Reserved. All trademarks are the property of their respective holders. The
information in this document is provided for informational use only and is subject to change. For further information or support,
go to www.tekron.com.
LED Indicators section for an explanation of the status.
To reset the unit, the power must be cycled. To cycle the power, it is recommended that the
external power source switch that the device the TCG 01-G is connected to; is turned OFF, wait
a full ten seconds, and then turned ON again. This will result in the TCG 01-G having to
resynchronize with the GNSS satellites.
Event Recording Function
General Description and Specification
TCG 01-G clocks can provide event recording (time tagging) on each input of
P6
. The P6 inputs A
and B are TTL level inputs with an input burden of 7 mA.
Recorded time tags contain timestamps corresponding to the rising edge of a pulse. The
minimum pulse duration is 1 µs, and the maximum rate of time tag recording is 100 tags per
second (aggregated over both inputs). In the event of pulses occurring simultaneously on both
inputs, both events are captured and recorded independently with the same time data.
The event recording option makes use of the same input connector (P6) as the
external IRIG-B input function.
The user can retrieve time tags from the buffer using a request/response protocol operating
over TCG 01-G’s P4 serial port interface. Tags are retrieved from the buffer oldest data first.
Refer to the Event Recording Specification section of the Appendix for more detail on the event
recording functionality, and a specification of the time tag format and the retrieval commands.
P6 Input Function (IRIG-B / Event Recording)
This feature provides a means to monitor /control signal activity on the two input channels of
P6
. The TCG 01-G clock supports both IRIG-B and event recording input functions on the two
P6
inputs. If one IRIG-B input function and one event input function are selected, then P6A is the
event input, and P6B is the IRIG-B signal input. As described in , when synced to IRIG-B, on the
bottom right of the LCD will show SL1 or SL2 to indicate synchronization with a source from P6A
or P6b respectively. Figure 10 below shows how the P6 IRIG-B input can be used to connect
multiple TCG 01-G units together.