P6: Event Recording / IRIG-B Sync Inputs (4-pin 3.81 mm Connector)
The pluggable connector provides two input channels that may be driven by
TTL sources. The input can be either be configured for a pulse for event
recording or for receiving un-modulated IRIG-B – IRIG-B004 with C37.118.1
extensions only. This option allows IRIG-B to be used as a secondary sync
source.
The input type is software configurable. If both event recording and IRIG-B sync input functions
are selected, then channel ‘A’ is the Event Input and channel ‘B’ is the IRIG-B sync input.
The expected input is 5 V, 7 mA, however inputs up to 10 V, 20 mA may be applied. The ‘+’ and
‘-’ symbols represent the positive and negative terminals respectively. The supported wiring
size is up to 1.00 mm².
The two ports are isolated from the rest of the system by a 2.5 kV barrier and the ports have a
60 VDC isolation from each other. Each input is protectively clamped to 25 V and uses a 470 Ω
resistor to limit the current.
Refer to the Event Recording Specification section of this manual for further information on the
event recording feature.
P7: Sync Relay (4-pin 3.81 mm Connector)
P7
provides two alarm output channels.
P7 A
is the GNSS signal receive fail (Antenna fail) alarm. The antenna alarm
only occurs after a continuous 5 seconds with the antenna disconnected or
short-circuited.
P7 B
is a synchronization fail alarm. This alarm is active (contact open) when
the unit is not synchronized and is not in the holdover state.
The alarm outputs are Type A (
normally-open
) dry contact types (implemented using solid state
relays).
Note
: the “
Normally-Open
” descriptor refers to the de-energized state of the relay.
The TCG 01-G operates with the alarm relays energized during normal operation, and de-
energized in the alarm state. In the case of all power to the clock being lost, all of the alarm
relays will default to the “alarm” state (open contact).
The “+” and “-” symbols are included for reference purposes only, as the alarm contacts are not
polarized. The supported wiring size is up to 1.00 mm², and the contact rating is 200 V, 150 mA
DC or 150 V, 100 mA AC.