TFP-40x Series Conventional Fire Alarm Panels
TFP-40X INSTALLATION & OPERATION MANUAL
3
1
Introduction
This manual contains the installation instructions, technical properties, and panel configuration information
related to TFP-40x Series Teknim Conventional Panels.
TFP-40x Teknim conventional panels may be viewed under 2 options as 4- or 8-zone devices. 32 detectors or
fire alarm buttons can be connected per zone.
TFP -40x series panels compliant with EN54-2/4 standards
Before installation, the manual must be read and installation must be carried out by authorized
persons in accordance with the instructions.
Before starting the installation, check that the following list is complete inside the package:
-
TFP-40x panel,
-
6 pieces of 4K7 siren end-of-line resistances for TFP-404 and 10 pieces for TFP-408,
-
Lock key for access level 2,
-
Battery cable,
-
Battery mounting lugs and 4 screws
-
4 screws and dowels for wall-mounting
-
Allen key,
-
Installation and Operation Manual
-
Quick Installation Manual
-
Warranty Certificate
2
Warnings
-
The panel contains electronic card consisting of digital and analog circuits. Therefore it should not be
used before having read the entire operation manual.
-
In case of any malfunction or in the case that the panel needs maintenance, maintenance and repairs
must be carried out by the authorized service station of the manufacturer company or the people/companies
authorized by the manufacturer company.
-
The cable lines for the supply line of the panel, siren line, and the detector line should be as specified in
this manual.
-
When panel is energized with supply voltage, do not make any changes to the panel connections.
-
The grounding connection to the panel must have been made.
-
Do not apply ~230 VAC 50Hz mains voltage to the inputs-outputs of the zone line, inputs of the siren
line connections, and the inputs of the battery connections.
-
Do not use batteries that have reached the end of useful life or have been damaged by falling below a
voltage level. The device does not charge batteries that are below voltage level 20.5 VDC.
Warning: Do not start mounting before having read the entire manual.