TFP-40x Series Conventional Fire Alarm Panels
TFP-40X INSTALLATION & OPERATION MANUAL
13
7.3
Siren Resound Option
As a default setting, when the panel first enters into fire status and the sirens are muted with the "Arm/Disarm"
button, if an alarm is detected from another zone, siren are automatically activated.
This can be changed as an option. If changed, sirens will not be reactivated for each new alarm detected after
the sirens are muted with the "Alarm On/Off" button.
To adjust this setting;
1
Enter Access Level-3.
2
Bring the "Siren Resound Option Switch" shown in "9.3 Appendix-Level /Figure 9 Level-3" to "ON"
position.
3
Restore access level to 1.
7.4
System Error
TFP-40x Teknim conventional panels are microcontroller-based systems. As per EN54-2 Article 13.3, the
microcontroller is controlled by another completely independent system. In the case that the microcontroller fails
to carry out program flow for any reason, the panel automatically takes itself into secure status. In this case, the
following occur:
1
General Error and System Error LEDs light up constantly. System On LED turns off.
2
Buzzer rings constantly. The buzzer can be silenced using the "Mute" button.
3
Energy to the zones and sirens is disconnected so as not to cause any false detection.
4
Trouble relay is activated.
WARNING!
In case of a system error, contact your dealer or authorized service station.
7.5
Error Diagnostic
In case of a fault, "General Error" LED and the related fault LED flashes. Situations detected as faults are given in
Table 6.
Table 6 Recognized Errors
LED name
Errors that may occur
General Error
Any faults
System Error
If the microcontroller is not operational for any reason
If the system voltage is below 14V
Supply Error
If there is no main power supply
If the battery charging circuit is faulty
Battery Error
If there is no battery
If the battery is empty
If the battery internal resistance is greater than 1.5 ohms
Earth Error
If the earth voltage is high
If the earth voltage is low
Siren Status
If the siren is open-circuited
If the siren is short-circuited
Zone
Error/Disable/Test
If the zone is open-circuited
If the zone is short-circuited
Open-circuit or short-circuit faults of the zones that might occur in installation is shown in more detail by the
panel for the convenience of the installer.
When the "Enter" button is pressed, the panel shows the details of the zone faults in more detail for 3 seconds.
During these 3 seconds, if the fault LED lights up constantly the zone is short-circuited and if it flashes the zone is
open-circuited.