background image

TFP-40x Series Conventional Fire Alarm Panels 

 

 

TFP-40X INSTALLATION & OPERATION MANUAL  

10 

 

In the case that main supply is interrupted, the smart charging unit automatically opens the battery connections 
and shut down the system to prolong the useful lifetime of the batteries when the battery voltage drops below 
20.5V. If the main supply is restored, the batteries automatically return to charging status. 

5.5 

Battery Charge Voltage Check 

Battery  charge  voltage  is  set  at  the  factory  as  27.6  VDC  at  20°C.  Therefore  there  is  no  need  to  readjust  the 

battery charge voltage. But if problems occur with battery charge, the following steps should be taken: 

1

 

After the battery is disconnected and the panel displays the error "No Battery", no voltage should be seen at 
the battery connector of the panel. 

2

 

The front cover of the panel should be opened and device shall be taken to Access Level-3. At this level, 
heat compensation of the smart charging system is deactivated. 

3

 

The output voltage of the main supply should be checked. In this case the output voltage should be 27.75 

±50

mV. If the output voltage is not at this level, the output voltage should be brought to this level via the 

adjustment potentiometer located near the power supply. 

4

 

When the adjustment of the output voltage of the power supply is completed, the panel should be brought 
back to access level-1. 

5

 

When  an  empty  battery  (~22V)  is  reconnected  to  the  panel,  it  must  be  seen  that  voltage  between  the 
battery poles rise rapidly. If not, there is a problem with the battery or the panel. 
 

5.6 

 Inputs and Outputs  

Relay Outputs: 

The panel has 2 dry-contact relay output that can withstand a current of 2A at 30 VDC. These 

dry-contact relays are fire relay (normally non-energized) and fault relay (normally energized). 

Important Note: 

The relays of the fire alarm panel are signal relays. If these relays are to operate a device 

as command relays, a contactor should be place in between. If a contactor is not used when the relay outputs 
are  used  in  an  application  that  draws  high  current,  then  the  panel  may  be  damaged  and  this  situation  is 

outside the warranty scope. 

Siren Outputs: 

The panel has 2 siren outputs of 24 V DC 500 mA with automatic return and fuse protection. 

Drawing too much current through this output causes to panel to give out faults. This output is monitored by the 
end-of-line resistance against  open circuits and short circuits. The cable of the  siren  supply line must  a 2x1.5-
mm2 cable. The connections are shown in "9.2 Appendix-Electrical / Figure 6 Siren Connection.

 

Alarm Relay: 

In case of a fire alarm from the detection zones or when the "Alarm On /Off " button on the front 

of the panel is pressed, it is activated by changing contacts and is used to control another system. In order for 
the active relay to be restored, the fire status has to be eliminated and the "Reset" button on the panel has to be 
pressed. 

Trouble Relay: 

It is activated by changing contacts in case of a fault alert from the system and when the power 

is not supplied to the panel. Trouble relay automatically returns to its previous position with the elimination of the 
fault status. 

AUX Output (External Supply Output): 

The panel has 24VDC 500mA external supply output with automatic 

fuse protection. In cases of blackouts, the external supply output is supplied until the battery reaches the cutoff 
voltage. 

5.7 

 Zone Lines 

TFP-40x Teknim conventional panels may be viewed under 2 options as 4- or 8-zone devices. Detection circuits 
provide power (24 VDC) to the detectors and buttons and at the same time ensures that signals like fire alarm, 
short  circuit,  and  broken  line  are  transmitted  to  the  panel  Maximum  32  detectors  or  alarm  buttons  can  be 
connected to a zone line. Cable coded 1x2x0,8+0,8JY(st)Y should be used for connection distances of 0  - 500 
meters and cable coded 1x2x1,5+1,5J-Y(st)Y for connection distances of 500 - 1500 meters. 

The form of connection of the zone line with the detector and alarm button is shown in "Appendix-Electrical / 
Figure 7 Zone Connection". Unused zones should be disabled over the panel or terminated with the termination 
resistance. If no connections are made to the zone, the panel gives the error "Zone Open Circuit". 

Zone  cables  should  be  kept  away  from  high-voltage  cables  that  may  cause  interference  at  the  site  and  from 
strong magnetic fields. Earthing of the signal cables must absolutely be made from the earthing bar inside the 
panel as shown "Figure 8 Zone Grounding Connection". 

Summary of Contents for TFP-40 Series

Page 1: ...2016 TFP 40x Series Conventional Fire Alarm Panel Installation Operation Manual Issue Date 26 12 2016 Rev 02 ...

Page 2: ...l 1 11 6 2 Level 2 11 6 3 Level 3 11 6 4 Level 4 11 7 Using the Panel 12 7 1 Disable Mode 12 7 2 Test Mode 12 7 3 Siren Resound Option 13 7 4 System Error 13 7 5 Error Diagnostic 13 8 Maintenance 14 8 1 Situations requiring Maintenance Repair or Servicing 14 8 2 Routine Checks 14 8 2 1 Daily 14 8 2 2 Weekly 14 8 2 3 4 Years 14 9 Appendices 15 9 1 Appendix Mechanical 15 9 2 Appendeix Electrical 19 ...

Page 3: ...ction 20 Figure 7 Zone Connection 20 Figure 8 Zone Grounding Connection 21 Figure 9 Level 3 22 1922 Bilgi Elektronik San ve Tic A Ş Dudullu OSB 1 Cad İsmet Tarman İş Merkezi No 1 Kat 2 32 Ümraniye İstanbul Turkiye 16 1922 CPD 0690 EN 54 2 1997 EN 54 2 1997 AC 1999 EN 54 2 1997 A1 2006 Control and indicating equipment for fire detection and fire alarm systems for buildings TFP 404 TFP 408 Provided ...

Page 4: ...Manual Quick Installation Manual Warranty Certificate 2 Warnings The panel contains electronic card consisting of digital and analog circuits Therefore it should not be used before having read the entire operation manual In case of any malfunction or in the case that the panel needs maintenance maintenance and repairs must be carried out by the authorized service station of the manufacturer compan...

Page 5: ...ine Resistance 4K7 ohm 5 1 4W General Error Relay 1 x NC NO dry contact 30V 2A Fire Relay 1 x NC NO dry contact 30V 2A Auxiliary Output AUX 1 x 24Vdc 450mA Caution The output current of the panel should not exceed 1 4 A AUX Fuse 1 x 500mA F3 Cable Type for Outputs 2 x 1 5mm J Y St Y Lg Recommended Zone Information Number Of Zones 4 or 8 Number of Detectors 32 pieces per zone TFD series Output 24Vd...

Page 6: ...e designed larger and in color to direct the user For the calculation of how long the system can be supplied via a battery after an interruption of the main supply the current consumptions of the panel are given in the table for uncharged and alarm statuses Model Idle Status Alarm Status TFP 404 75 mA 140 mA TFP 408 115 mA 180 mA 4 1 Panel Properties 4 or 8 zones controlled against incorrect conne...

Page 7: ...sk C ALARM On Off Shall be used in Level 2 and Level 3 Starts the evacuation procedure activates sirens Mutes sirens in alarm status or resounds the muted sirens D MUTE Mutes Buzzer in cases of fault or alarm E RESET Shall be used in Level 2 and Level 3 Used to restore the panel in alarm or fault status to normal operating status The buttons F G and H shown in Figure 1 Control Panel User Interface...

Page 8: ...Level 1 H TEST It is used to test the buzzer and the LEDs in Level 1 It is used to change the processed zone or siren when disable process is active in Level 2 Also it is used to show the tested zones and siren for 3 seconds when test and disable processes are deactivated It is used to show the zones and siren being tested for 3 seconds in Level 1 It is used to turn on and off the test process in ...

Page 9: ... the earth connection Yellow N Siren Status Shows that the siren is disabled Shows there is a fault in the siren Yellow O Energy Shows that the system is supplied from any source NONE Green P System Activated Shows that there no problems that can affect the full operation of the system NONE Green R Test Shows that one or more zones are in test status NONE Yellow S Disable Shows that the zones or t...

Page 10: ...e holes marked on the wall and complete the fixing process with minimum 4 mm dowel and screws 4 Then proceed to battery and cable connection processes 5 3 Supply Input The panel main supply input should be connected to the 195 250 VAC 50 Hz mains voltage and earth connection must be made It should be ensured that grounding resistance is less than 10 ohms The main supply input fuse of the panel mus...

Page 11: ...uts The panel has 2 siren outputs of 24 V DC 500 mA with automatic return and fuse protection Drawing too much current through this output causes to panel to give out faults This output is monitored by the end of line resistance against open circuits and short circuits The cable of the siren supply line must a 2x1 5 mm2 cable The connections are shown in 9 2 Appendix Electrical Figure 6 Siren Conn...

Page 12: ...and activating zones sirens Zone test Evacuation status creation Muting or reactivating sirens in an alarm situation Resetting alarm or fault statuses To leave Level 2 turn the key into vertical position and remove it 6 3 Level 3 All the authorizations and functions of the system can be performed at this level The users of this system are authorized persons who have received training on system ins...

Page 13: ...ction system can be conducted by a single person When a fire signal is received from the detectors or fire alarm buttons from a zone being tested the panel enters into fire status If sirens are selected in the test mode the panel activates also the panel outputs and resets itself after 10 s Test mode settings can be adjusted from access levels 2 3 and 4 In order to test a zone or a siren Test butt...

Page 14: ...rgy to the zones and sirens is disconnected so as not to cause any false detection 4 Trouble relay is activated WARNING In case of a system error contact your dealer or authorized service station 7 5 Error Diagnostic In case of a fault General Error LED and the related fault LED flashes Situations detected as faults are given in Table 6 Table 6 Recognized Errors LED name Errors that may occur Gene...

Page 15: ...vice station Only qualified and authorized servicing personnel should carry out technical interventions on the device The device should be cleaned with a dry cloth No chemicals should be used 8 2 Routine Checks 8 2 1 Daily The authorized person should check the device daily for any fault statuses The green Energy and System On LEDs on the panel should be lit 8 2 2 Weekly Fire alarm systems should ...

Page 16: ... Fire Alarm Panels TFP 40X INSTALLATION OPERATION MANUAL 15 9 Appendices The Appendices are divided into 4 categories a Mechanical Electrical Level and Maintenance Tables 9 1 Appendix Mechanical Figure 2 Panel Front Cover Screws ...

Page 17: ...TFP 40x Series Conventional Fire Alarm Panels TFP 40X INSTALLATION OPERATION MANUAL 16 Figure 3 Mounting Screw Holes A2 Mounting Screw Hole ...

Page 18: ...nels TFP 40X INSTALLATION OPERATION MANUAL 17 Figure 4 Electrical Connections A3 Battery Connection Connector A4 Main Supply Connection Connector A5 Main Supply Voltage Adjustment Potentiometer A6 Button for Startup from Battery A7 Mains Fuse ...

Page 19: ...y rails shown as B1 are fixed with screws B4 and B5 are connected to each other with jumper cable B2 and B3 are connected to the battery supply socket with battery supply cable Do not use batteries that have reached the end of useful life or have been damaged by falling below a voltage level The device does not charge batteries that are below voltage level 20 5 VDC ...

Page 20: ...TFP 40x Series Conventional Fire Alarm Panels TFP 40X INSTALLATION OPERATION MANUAL 19 9 2 Appendix Electrical Figure 6 Siren Connection Figure 7 Zone Connection ...

Page 21: ...TFP 40x Series Conventional Fire Alarm Panels TFP 40X INSTALLATION OPERATION MANUAL 20 Figure 8 Zone Earth Connections ...

Page 22: ...tional Fire Alarm Panels TFP 40X INSTALLATION OPERATION MANUAL 21 9 3 Appendix Level Şekil 1 Seviye 3 C1 Computer Communication Connector C2 Switch for Siren Resound Option C3 Access Level 3 Activation Key C4 Hardware Reset ...

Page 23: ...TFP 40x Series Conventional Fire Alarm Panels TFP 40X INSTALLATION OPERATION MANUAL 22 9 4 Appendix Maintenance Table Date Tested Device Device Position Remarks ...

Page 24: ...TFP 40x Series Conventional Fire Alarm Panels TFP 40X INSTALLATION OPERATION MANUAL 23 Date Tested Device Device Position Remarks ...

Page 25: ...TFP 40x Series Conventional Fire Alarm Panels TFP 40X INSTALLATION OPERATION MANUAL 24 Date Tested Device Device Position Remarks ...

Page 26: ...TFP 40x Series Conventional Fire Alarm Panels TFP 40X INSTALLATION OPERATION MANUAL 25 Date Tested Device Device Position Remarks ...

Page 27: ...he device should be carried carefully so as not to subject it to any external impacts and to prevent liquid penetration Malfunctions arising due to improper handling are outside the scope of warranty Complies with Directive 2002 96 EC This product is produced from recyclable and reusable high quality parts and materials Therefore do not dispose of the product together with the household or other w...

Reviews: