background image

Shifting the Heating Curve

(a) Manually, at the control:

The Occupied and Unoccupied dials on this control can shift the WWSD
point up or down from 35 to 105

°

F (2 to 41

°

C).

(b) Automatically, using room temperature feedback:

In addition to a Supply Sensor and an Outdoor Sensor, this control can use
a tekmar RTU, Zone Control or Indoor Sensor to provide room temperature
feedback for added comfort and system flexibility.

The control still calculates a desired supply temperature based on the
Heating Curve setting and the outdoor temperature.

If the air temperature in the room is too cold, the control will shift the Heating
Curve (and WWSD point) 

up, which raises the supply temperature until the

room warms up again.

If the air temperature in the room is too warm, the control will shift the Heating
Curve (and WWSD point) 

down, which lowers the supply temperature until

the room cools down.

Correct setting and shifting of the Heating Curve...   the key to More Comfort and Energy Savings.

Heating Curve

As outdoor temperatures become colder, heat losses from a building increase, which requires the addition of more heat to prevent
the indoor air temperature from also becoming colder.  This tekmar reset control measures the outdoor temperature and as the outdoor
temperature becomes colder, it balances the heat loss by making the heating supply water hotter.
The Heating Curve is used to calculate exactly how hot to make the supply water at different outdoor temperatures.  It determines
the number of degrees the supply water temperature is raised for each degree the outdoor temperature falls.

Setting the Heating Curve

Two examples of how the Heating Curve works are illustrated in the following diagram.

—With a 2.4 Curve, the supply water temperature is raised 2.4 degrees for every degree of outdoor temperature drop.

If:  WWSD point = 70

°

F and Outdoor temperature = 30

°

F, then supply temperature = 166

°

F

—With a 0.6 Curve, the supply water temperature is raised 0.6 degrees for every degree of outdoor temperature drop.

If:  WWSD point = 70

°

F and Outdoor temperature = 30

°

F, then supply temperature = 94

°

F

2

• If the Heating Curve selected is too low;  the heating system will not

supply hot enough water to keep the room temperature warm during
colder weather.

• If the Heating Curve selected is too high;  the supply water will be too hot

for the conditions and the building will overheat during colder weather.

Warm Weather Shut Down (WWSD)

At warm outdoor temperatures, the indoor space of a building gains heat
from the outdoors; additional heat is not required, and if the heating system
is running (even on standby), enough excess heat can be produced to
overheat the building, causing discomfort and wasting valuable energy.
This control shuts off the boiler(s) and system pump when the outdoor
temperature is above the WWSD point.

As outdoor temperatures get colder, there comes a point where the heat
gain turns into heat loss; the heat loss causes the indoor temperature to fall
below the comfort level, and the heating system must be turned on to start
delivering heat.

Refer to the tekmar Essays E 001 and E 002 for more detailed information regarding control strategy and integration of control functions.

A very cool room temperature can shift the curve far enough up to bring the control out of WWSD at warm outdoor temperatures.
A very warm room temperature can shift the curve far enough down to put the control into WWSD at cool outdoor temperatures.

To provide heat to the building, this control turns on the system pump and cycles the boiler(s) to deliver heat at the low output required
by the Heating Curve near the WWSD point.

When the system is operating near the WWSD point and the building is too cold;   the WWSD point should be raised.
When the system is operating near the WWSD point and the building is too warm;   the WWSD point should be lowered.

Outdoor Reset Strategy

Outdoor air  temperature

Supply water temperature

50

(10)

30

(-1)

10

(-12)

-10

°

F

(-23)

°

C

110

(43)

70

(21)

70

(21)

90

(32)

210

(99)

170 

(77)

150 

(65)

130 

(54)

190

(88)

3.6 3.0 2.4 2.0

1.6

0.8

0.4

1.0

0.6

90

(32)

50

°

F

(10)

°

C

Heating

Curve

WWSD

Point

1.2

Outdoor air  temperature

Supply water temperature

50

(10)

30

(-1)

10

(-12)

-10

°

F

(-23)

°

C

110

(43)

70

(21)

70

(21)

90

(32)

210

(99)

170 

(77)

150 

(65)

130 

(54)

190

(88)

3.6 3.0 2.4 2.0

1.6

0.8

0.4

1.0

90

(32)

50

°

F

(10)

°

C

Heating

Curve

WWSD

Point 

will 

shift 

up and 

down 

with 

shift of 

Heating 

Curve

1.2

UP

DOWN

UP

DOWN

Parallel Shift of Heating Curve

0.6

Summary of Contents for DHW Control 252

Page 1: ...n order to satisfy the DHW requirements D 252 Operating Mode selector switches Terminal Plugs Power and out put connections Terminal Plug Sensor and timer inputs Outdoor Reset Strategy pg 2 Testing pg...

Page 2: ...lected is too low the heating system will not supply hot enough water to keep the room temperature warm during colder weather If the Heating Curve selected is too high the supply water will be too hot...

Page 3: ...emperature supply temperature and indoor temperature optional Whenever 3 days pass with the control in uninterrupted WWSD the system pump will be cycled on for 20 seconds to help prevent it from seizi...

Page 4: ...mperature reaches the heating curve desired temperature plus one half thedif ferential setting where the Stage light s will turn off and the boiler s will be shut off Note Whenever the boiler s are tu...

Page 5: ...nnections The installer should test to confirm that no voltage is present at any of the wires Install the control into the base sliding it down until it snaps into place All electrical connections are...

Page 6: ...2K RTU Com Sen 20 Sup Sen 21 Out Sen Com Sen 22 Stage DHW DHW Sensor optional 071 DHW Sen DHW 10K Indoor Sensor 074 or Zone Control optional 10A 10A 10A DHW Demand When DHW requested and there is no D...

Page 7: ...and ensure that it is powered up and the voltage is correct Check the devices in the circuit limits flow switches etc for faults If the boiler operates properly when the circuit is powered up disconn...

Page 8: ...ls Com Sen UnO Sw 17 and 18 are shorted out the control switches from operating at the Occupied dial setting to operating at the Unoccupied dial setting When a tekmar Zone Control or 2K RTU RoomTemper...

Page 9: ...C above the desired temperature Delays of 8 seconds to 3 minutes for staging off depend on the degree of control error Within the differential range no boilers are staged on or off Trial setting 22 F...

Page 10: ...mp will remain on After the 5 minutes the control will automatically exit the test routine and enters the normal operating mode If there is no DHW Demand the control will not allow a pause and will pr...

Page 11: ...door Sensor or RTU input becomes shorted out the Occupied and Unoccupied dial settings will become active After any repair has been completed press the Test button to allow the control to cycle throug...

Page 12: ...bour to remove transport or reinstall a defective product tekmar will not be liable for any damage other than repair or replacement of the defective part or parts and such repair or replacement shall...

Reviews: