background image

Heating Curve  =

For example:

•  design outdoor temperature =  5

°

F (-15

°

C)

•  room temperature =  70

°

F (21

°

C)

•  design supply temperature =  160

°

F (71

°

C)

Heating Curve  =

  =

  =   1.4

8

Heating Curve

As outdoor temperatures drop, heat losses from a space become
greater and the heating system supply water temperature must be
raised to maintain a constant room temperature.  The heating curve
value describes how many degrees the supply water temperature is
raised for a one degree drop in outdoor temperature.  The supply
temperature starts to increase when the outdoor temperature falls
below the WWSD point.  To calculate the correct setting for the Heating
Curve, use the following formula.

design supply temperature – room temperature

room temperature – design outdoor temperature

0.4

2.0

3.6

Heating Curve

Outdoor air  temperature

Supply water temperature

50

(10)

30

(-1)

10

(-12)

-10

°

F

(-23)

°

C

110

(43)

70

(21)

70

(21)

90

(32)

210

(99)

170 

(77)

150 

(65)

130 

(54)

190

(88)

3.6 3.0 2.4 2.0

1.6

0.8

0.4

1.0

0.6

90

(32)

50

°

F

(10)

°

C

Heating

Curve

WWSD

Point

1.2

160

°

F - 70

°

F

70

°

F - 5

°

F

90

°

F

65

°

F

For more information regarding the Heating Curve, refer to page 2 of this brochure.  If the actual designed supply water temperature
for a system is unknown, a trial setting can be calculated using these typical supply temperatures:
• Fan coils …180

°

 to 210

°

F (82

°

 to 99

°

C)   • Baseboards …160

°

 to 190

°

F (71

°

 to 88

°

C)   • Radiant floors …100

°

 to 130

°

F (38

°

to 54

°

C).

Occupied temperature

When there is no room temperature feedback to the control, the Occupied dial setting determines the starting
point of the heating curve (WWSD point) and the Heating Curve setting will reset the water temperature as
described in the Heating Curve instructions above.
When an Indoor Sensor 074 is connected to the control, the Occupied dial setting becomes the actual controlled
temperature of the room.  This feature will help the control compensate for an incorrectly set heating curve
or for unexpected internal heat gains or losses.  If the room temperature is too high or too low, the indoor
sensor allows the heating curve to be shifted up or down accordingly.
When a tekmar Zone Control or 2K RTU (Room Temperature Unit) is connected to the control, the RTU

setting

becomes the controlled temperature and the Occupied dial becomes inactive.

Unoccupied temperature

The Unoccupied dial operates in the same way as the Occupied dial.
When the terminals 

Com Sen — UnO Sw (17 and 18) are shorted out, the control switches from operating

at the Occupied dial setting to operating at the Unoccupied dial setting.  When a tekmar Zone Control or 2K
RTU (Room Temperature Unit) is connected to the control, the RTU setting becomes the controlled temperature
and the Unoccupied dial becomes inactive.

Zone Control/Indoor Sensor switch

When this selector switch is in the "Indoor Sensor" position, and a tekmar Indoor Sensor 074 or a tekmar 2K
RTU is connected, the control receives room temperature feedback from the RTU or Indoor Sensor and the
Occupied/Unoccupied dials operate as described above.
When the switch is in the "Zone Control" position, and a tekmar Zone Control is connected, the control receives
information from the Zone Control that allows the heating curve to be shifted so the supply water temperature
is hot enough to satisfy the requirements of the zone with the highest heat demand.

DHW

When the control receives a DHW Demand signal from either a DHW Sensor or from 24V applied to the
DHW Dem terminals, the control will operate in the DHW mode.

  See DHW operation, pg. 4

DHW during Unoccupied mode

When this selector switch is in the "On" position, DHW will continue to be generated when the control is
switched into the Unoccupied mode and a DHW Demand signal is received.  When the switch is in the "Off"
position, the DHW mode becomes inactive when the control is in Unoccupied mode and the control will ignore
any DHW Demand signal.

DHW Priority switch

When this selector switch is in the "On" position, DHW generation will be given priority over heating operation
when a DHW Demand signal is received.  When the switch is in the "Off" position, DHW generation is

simultaneous with heating operation.  

See Application Brochure A 252.

DHW Valve/Pump switch

Set this selector switch to the "Valve" position when a valve is used in DHW generation and the "Pump"
position when using a pump.  

See Application Brochure A 252.

Occupied

35 
(2)

105
(41)

70

°

F

(21

°

C)

140

°

F

80

200

DHW

35 
(2)

105
(41)

70

°

F

(21

°

C)

Unoccupied

1

2

3

4

5

6

7

8

Auto

Stage

1   2

Perm. Heat Demand

External Heat Demand

Indoor sensor

Zone control

DHW during unoccupied

DHW priority

Rotate

Off

DHW valve

DHW pump

1

2

3

4

5

6

7

8

Auto

Stage

1   2

Perm. Heat Demand

External Heat Demand

Indoor sensor

Zone control

DHW during unoccupied
DHW priority

Rotate

Off

DHW valve

DHW pump

1

2

3

4

5

6

7

8

Auto

Stage

1   2

Perm. Heat Demand

External Heat Demand

Indoor sensor

Zone control

DHW during unoccupied

DHW priority

Rotate

Off

DHW valve

DHW pump

Summary of Contents for DHW Control 252

Page 1: ...n order to satisfy the DHW requirements D 252 Operating Mode selector switches Terminal Plugs Power and out put connections Terminal Plug Sensor and timer inputs Outdoor Reset Strategy pg 2 Testing pg...

Page 2: ...lected is too low the heating system will not supply hot enough water to keep the room temperature warm during colder weather If the Heating Curve selected is too high the supply water will be too hot...

Page 3: ...emperature supply temperature and indoor temperature optional Whenever 3 days pass with the control in uninterrupted WWSD the system pump will be cycled on for 20 seconds to help prevent it from seizi...

Page 4: ...mperature reaches the heating curve desired temperature plus one half thedif ferential setting where the Stage light s will turn off and the boiler s will be shut off Note Whenever the boiler s are tu...

Page 5: ...nnections The installer should test to confirm that no voltage is present at any of the wires Install the control into the base sliding it down until it snaps into place All electrical connections are...

Page 6: ...2K RTU Com Sen 20 Sup Sen 21 Out Sen Com Sen 22 Stage DHW DHW Sensor optional 071 DHW Sen DHW 10K Indoor Sensor 074 or Zone Control optional 10A 10A 10A DHW Demand When DHW requested and there is no D...

Page 7: ...and ensure that it is powered up and the voltage is correct Check the devices in the circuit limits flow switches etc for faults If the boiler operates properly when the circuit is powered up disconn...

Page 8: ...ls Com Sen UnO Sw 17 and 18 are shorted out the control switches from operating at the Occupied dial setting to operating at the Unoccupied dial setting When a tekmar Zone Control or 2K RTU RoomTemper...

Page 9: ...C above the desired temperature Delays of 8 seconds to 3 minutes for staging off depend on the degree of control error Within the differential range no boilers are staged on or off Trial setting 22 F...

Page 10: ...mp will remain on After the 5 minutes the control will automatically exit the test routine and enters the normal operating mode If there is no DHW Demand the control will not allow a pause and will pr...

Page 11: ...door Sensor or RTU input becomes shorted out the Occupied and Unoccupied dial settings will become active After any repair has been completed press the Test button to allow the control to cycle throug...

Page 12: ...bour to remove transport or reinstall a defective product tekmar will not be liable for any damage other than repair or replacement of the defective part or parts and such repair or replacement shall...

Reviews: