background image

9

Boiler Differential

The Boiler Differential adjustment sets how much the actual
supply water temperature may deviate from the desired
temperature before stages are turned on or off, and is
determined by the flow rate past the supply sensor relative
to the amount of heat produced by each stage.  To prevent
short operating cycles of the boiler(s) the control has a delay
of at least 1 minute between firing cycles. On an installation
where flow rates are known, the Boiler Differential can be
calculated as follows:

Outdoor air  temperature

Supply water temperature

50

(10)

30

(-1)

10

(-12)

-10

°

F

(-23)

°

C

110

(43)

70

(21)

70

(21)

90

(32)

210

(99)

170 

(77)

150 

(65)

130 

(54)

190

(88)

3.6 3.0 2.4 2.0

0.8

0.4

1.0

0.6

90

(32)

50

°

F

(10)

°

C

Heating

Curve

1.2

Minimum Supply

Setting 130

°

F

WWSD

Point

70

°

F

1.6

120

°

F

Off

170

Minimum

Supply

80

Minimum Supply Temperature

This dial should be set according to the requirements specified by the
boiler manufacturer.  Many boilers require a minimum operating
temperature to prevent corrosion from flue gas condensation.  The
control raises the supply temperature to the Minimum setting when the
outdoor temperature drops below the WWSD point, and holds it there
until the outdoor temperature becomes cold enough to require opera-
tion on the heating curve.  When an Indoor Sensor 074 or 2K RTU is
installed in a room and the selector switch set for "Indoor Sensor", the
control will cycle the boiler on and off at the Minimum Supply tempera-
ture to prevent overheating of the room.

Typical Minimum Boiler Operating Temperatures:  • Steel Tube
Boilers …140

°

 to 180

°

F (60

°

 to 82

°

C) • Cast Iron Boilers …130

°

 to

150

°

F (54

°

 to 66

°

C) • Copper Tube Boilers …105

°

 to 150

°

F (41

°

 to

66

°

C) • Condensing or Electric Boilers …Off

100,000 Btu/hr

20 US GPM x 500

Btu/hr

US GPM x 500

Boiler Differential =

For example:

=

10

°

F (6

°

C)

All boilers will eventually turn on when the temperature falls 5

°

F (3

°

C) below the desired

temperature.  Delays of 1 to 5 minutes for staging on depend on the degree of control error.
All boilers eventually turn off when the temperature rises 5

°

F (3

°

C) above the desired

temperature.  Delays of 8 seconds to 3 minutes for staging off depend on the degree of
control error.  Within the differential range, no boilers are staged on or off.

Trial setting = 22

°

F if

flow rates are unknown

22

°

F

2

42

Boiler 

Differential

Test button

The control can be made to cycle through a test routine whenever the Test button is pushed.  The test can
be halted at certain times by pushing the button a second time.  For details of the test routine, refer to the
description starting on page 10.

Test

Indicator lights

There are eleven LEDs on the front of the control that will aid in testing and troubleshooting.  During normal operation, these lights
indicate the following functions:

Power light on

• the 24Vac power supply has been connected and the control is energized.

Heat Demand light on

• the control is receiving a 24Vac external Heat Demand signal at terminals 

Heat Dem — Heat

Dem (1 and 2) or the Heat Demand selector switch is in the "Permanent" position or a 10K Zone
Control causes a Heat Demand.

DHW Demand light on

•  the control is receiving a 24Vac DHW Demand signal at terminals 

DHW Dem — DHW Dem

(3and 4) or a DHW sensor is connected and has determined a need for DHW generation.

WWSD light on

• the outdoor temperature is above the WWSD point and the control has shut the heating system off.

Unoccupied light on

• the terminals 

Com Sen — Uno Sw (17 and 18) are shorted together, switching the control into

Unoccupied (setback) mode.

Minimum light on

• the control has calculated that it must operate the boiler(s) to maintain the Minimum Supply

temperature since the outdoor temperature is not cold enough for Heating Curve operation.

System pump light on

• the system pump relay is on, closing the contacts between terminals 7 & 8.

DHW pump light on

• the DHW pump/valve relay is on, closing the contacts between terminals 9 & 10.

Stage 1 or 2 light on

• a boiler relay is on, closing the contacts between terminals 11 & 12 or 13 & 14.

Test light on / flashing

• the control is going through the programmed test routine / is halted.

Desired temperature
this example
160

°

F(71

°

C)

T

emperature

W

armer

Cooler

Time

Differential

this example 

10

°

F(5

°

C)

165

°

F(74

°

C)

155

°

F(68

°

C)

Te

m

p

e

ra

tu

re

 fa

ll

Staging

OFF             ON

Te

m

p

e

ra

tu

re

 r

is

e

Summary of Contents for DHW Control 252

Page 1: ...n order to satisfy the DHW requirements D 252 Operating Mode selector switches Terminal Plugs Power and out put connections Terminal Plug Sensor and timer inputs Outdoor Reset Strategy pg 2 Testing pg...

Page 2: ...lected is too low the heating system will not supply hot enough water to keep the room temperature warm during colder weather If the Heating Curve selected is too high the supply water will be too hot...

Page 3: ...emperature supply temperature and indoor temperature optional Whenever 3 days pass with the control in uninterrupted WWSD the system pump will be cycled on for 20 seconds to help prevent it from seizi...

Page 4: ...mperature reaches the heating curve desired temperature plus one half thedif ferential setting where the Stage light s will turn off and the boiler s will be shut off Note Whenever the boiler s are tu...

Page 5: ...nnections The installer should test to confirm that no voltage is present at any of the wires Install the control into the base sliding it down until it snaps into place All electrical connections are...

Page 6: ...2K RTU Com Sen 20 Sup Sen 21 Out Sen Com Sen 22 Stage DHW DHW Sensor optional 071 DHW Sen DHW 10K Indoor Sensor 074 or Zone Control optional 10A 10A 10A DHW Demand When DHW requested and there is no D...

Page 7: ...and ensure that it is powered up and the voltage is correct Check the devices in the circuit limits flow switches etc for faults If the boiler operates properly when the circuit is powered up disconn...

Page 8: ...ls Com Sen UnO Sw 17 and 18 are shorted out the control switches from operating at the Occupied dial setting to operating at the Unoccupied dial setting When a tekmar Zone Control or 2K RTU RoomTemper...

Page 9: ...C above the desired temperature Delays of 8 seconds to 3 minutes for staging off depend on the degree of control error Within the differential range no boilers are staged on or off Trial setting 22 F...

Page 10: ...mp will remain on After the 5 minutes the control will automatically exit the test routine and enters the normal operating mode If there is no DHW Demand the control will not allow a pause and will pr...

Page 11: ...door Sensor or RTU input becomes shorted out the Occupied and Unoccupied dial settings will become active After any repair has been completed press the Test button to allow the control to cycle throug...

Page 12: ...bour to remove transport or reinstall a defective product tekmar will not be liable for any damage other than repair or replacement of the defective part or parts and such repair or replacement shall...

Reviews: