
Step Six
Essential control settings
To obtain the best operation from a reset control, it is important to measure the system supply temperature as accurately
as possible. Whenever the control receives a heat demand signal, the system pump must be operated to maintain
continuous water flow past the supply temperature sensor.
For specific application details refer to Application Brochure A 252.
A more detailed technical description of the effect of control settings on overall system operation is described in the tekmar Essay E 002.
Test the power supply
Make sure exposed wiring or bare terminals are not in contact with any other wires or grounded surfaces. Turn on the power to the
transformer and use an AC voltmeter to measure the voltage between terminals
C — R (5 and 6). 22 to 26 Volts AC should be measured
at these terminals.
Test the powered inputs
If an external Heat Demand signal is used, power up the Heat Demand circuit and supply a Heat Demand signal to the control. Use
an
AC voltmeter to measure the voltage between terminals
Heat Dem — Heat Dem (1 and 2). 22 to 26 Volts AC should be
measured at
these terminals.
If a DHW Demand signal is used, power up the DHW Demand circuit and supply a DHW Demand signal to the control. Use an AC
voltmeter to measure the voltage between terminals
DHW Dem — DHW Dem (3 and 4). 22 to 26 Volts AC should be measured at these
terminals.
If a System Pump circuit is connected to the
Sys Pmp — Sys Pmp (7 and 8) terminals; make sure power to the circuit is off and install
a jumper in the terminal plug between terminals 7 and 8. When the circuit is powered-up, the pump should operate. If it does not
come on, check the circuit wiring for errors and ensure that it is powered up and the voltage is correct. Check the devices in the circuit
(pump, switching relay, etc.) for faults. If the pump operates properly when the circuit is powered up, disconnect the power and remove
the jumper. Repeat this step for the DHW pump / valve circuit.
Make sure power to the Boiler circuit is off and install a jumper in the terminal plug between the
Stage 1(11 and 12) terminals. When
the circuit is powered-up, the boiler should operate. If it does not come on, check the circuit wiring for errors and ensure that it is
powered up and the voltage is correct. Check the devices in the circuit (limits, flow switches, etc.) for faults. If the boiler operates
properly when the circuit is powered up, disconnect the power and remove the jumper. Repeat for Stage 2.
Caution
The tekmar Two Stage Boiler & DHW Control 252 is an operating control and is not certified or intended
for use as a safety device. Under no circumstances should safety limit devices be left disconnected
after installation of this control. The installer shall check all applicable code requirements and obtain
necessary inspections to ensure that the installation is in compliance with those requirements.
7
Terminal plug pushed into
its header on the control
Settings
15 16 17
19
18
20 21 22
10K
Sen
Com
Sen
Sup
Sen
DHW
Sen
UnO
Sw
Com
Sen
Out
Sen
2K
RTU
Connect the control
Turn the power off and make sure all test jumpers have been removed from the
plugs.
Connect the plugs to the control by carefully aligning them with their respective headers
and pushing them upwards into the headers. The plugs should snap firmly into place.
The control is now ready for set-up and operation.
Heat Demand switch
When the heating system uses zone valve end switches or some other means of delivering an
external heat demand signal to terminals
Heat Dem — Heat Dem (1 and 2), set this selector switch
to "External (1 & 2)" and the control will be enabled when it receives a 24Vac signal from the heat
demand circuit.
If an external heat demand signal is not used, set the switch to "Permanent".
Stage 1 & 2 Auto or Off switch
When a Stage switch is set to "Auto", that stage becomes active and its boiler is available. If the
Stage switch is "Off", the control will ignore that stage and not turn it on.
Rotate switch
When set to "Rotate", the firing order of the boilers will change whenever one stage accumulates
48 hrs more running time than the other. When set to "Off", Stage 1 is always the lead boiler.
1
2
3
4
5
6
7
8
Auto
Stage
1 2
Perm. Heat Demand
External Heat Demand
Indoor sensor
Zone control
DHW during unoccupied
DHW priority
Rotate
Off
DHW valve
DHW pump
1
2
3
4
5
6
7
8
Auto
Stage
1 2
Perm. Heat Demand
External Heat Demand
Indoor sensor
Zone control
DHW during unoccupied
DHW priority
Rotate
Off
DHW valve
DHW pump
1
2
3
4
5
6
7
8
Auto
Stage
1 2
Perm. Heat Demand
External Heat Demand
Indoor sensor
Zone control
DHW during unoccupied
DHW priority
Rotate
Off
DHW valve
DHW pump