Adjust Menu (3 of 4)
SLAB MAXIMUM
Maximum slab temperature. This item is only available in the
Installer access level.
(Must have an active slab sensor.)
34 to 122°F, OFF (1.0 to 50.0°C, OFF)
SENSOR 1
Selects the type of auxiliary sensor present in the Sen 1 input. This
item is only available in the Installer access level.
OFF, Indr, SLAB, REM
SENSOR 2
Selects the type of auxiliary sensor present in the Sen 2 input. This
item is only available in the Installer access level.
OFF, Indr, SLAB, OUT
ROOM SENSOR
Selects whether the built-in sensor is functional or not. This item
is only available in the Installer access level.
OFF, ON
HEATING CYCLE
Determines the number of cycles per hour for the heating
equipment. This item is only available in the Installer access level.
Auto, 2 to 12
COOLING CYCLE
Determines the number of cycles per hour for the cooling equipment.
This item is only available in the Installer access level.
Auto, 2 to 12
COOLING INTERLOCK
Selects the time delay between the heating and cooling relays. This
item is only available in the Installer access level.
10 to 180 min.
COOLING MINIMUM ON
Sets the minimum on time of the cooling contact. This is to prevent
short cycling. This item is only available in the Installer access level.
0:30 to 5:00 min.