35
CS
TECHNICAL DATA
Model
CS 130
CS 190
Drying capacity
l/24h
160
(1)
240
(1)
Rated power consumption (without electric heaters)
kW
1,89
(3)
3,0
(3)
Rated power consumption (with electric heaters)
kW
5,89
(3)
7,0
(3)
Maximum power consumption (without electric heaters)
kW
2,19
(2)
4,9
(2)
Maximum current consumption (without electric heaters)
A
10,7
(2)
10,4
(2)
Maximum power consumption (with electric heaters)
kW
6,19
(2)
8,9
(2)
Maximum current consumption (with electric heaters)
A
28,1
(2)
19,1
(2)
Start up current
L.R.A.
51
4,0
46
Rated air flow
m
3
/s
m
3
/h
0,42
1500
0,56
Available static pressure
Pa
90
2000
refrigerant charge (see label)
Type
R410A
100
Sound pressure level
(3m free field)
dB(A)
54
R410A
7-35
55
Temperatute operating range
°C
1-35
(4)
-1-35
(5)
7-35
Humidity operating range
%
40-99
1-35
(4)
-1-35
(5)
Condensed Water draining connection
“
¾’’ M
40-99
Lenght
mm
976
¾’’ M
Depth
mm
682
976
Height
mm
580
682
Operating weight
kg
66
580
Rated Power Supply
V/ph/Hz
230/1/50
72
(1) Referred to: inlet air temp. 32 °C relative humidity 90%
(2) Referred to: inlet air temp. 35 °C relative humidity 70%
(3) Referred to: inlet air temp. 26.7 °C relative humidity 60%
(4) S version with hot gas defrost
(5) BT version for low temperatures