34
CS
ELECTRIC BOX
The electric switch board is made according to Electromagnetic Compatibility Norms (2004/108 CE)
and Electrical Safety Rules for the Low Tension Appliances (2006/95 CE).
Inside the electric box there are the following components:
1. General disconnector with fuses;
2. Phase Sequenze relay;
3. Compressor Contactors;
4. Relays;
5. Terminals for remote control.
MICROPROCESSORS
The microprocessors check all the function of the machine like: General functioning, automatic
defrost system, alarms and set point of the humidty and temperature (only for TCR Version).
VERSIONS
AVAILABLE MODELS AND THEIR ACCESSORIES
HOT GASDEFROST VERSION (S):
the frost which covers the battery, obtrsucts the passage of the air,
reduces the air contact surface and, consequently, the performance; if the frost accumulation is
excessive, it can seriously damage the whole system. All units are provided with Desfrost System. The
defrosting is controlled by the electronic system in combination with a thermostat, whose bulb is
installed inside the evaporator.
The standard versions have their defrost simply throughly the periodic stop of the compressor and fan
ventilation, using the heat of the environment itself. In the versions with Hot Gas Defrost System, fan
turns off and compressor continues to work in order to melt the ice in the evaporator.
During the defrosting time the DEFROST light is ON.
HEATERS VERSION (+4kW) :
these units are provided with electrical heaters to increase outlet air
temperature.
TEMPERATURE CONTROL VERSION (TCR):
the units for the control temperature version are
equipped with external remote condenser that is connected with the dehumidifier. The use of the
remote condenser allows the control of the temperature and humidity at the same time, operating in
cooling or dehumidifying mode. In order to use both functions it’s necessary to have a thermostat and
an hygrostat.
The regulation can be ON/OFF or modulating.
INOX COVER VERSION (INOX):
these units are provoded with the external cover made of stainless
steel.