![TECO T-verter N2 Series Operation Manual Download Page 55](http://html1.mh-extra.com/html/teco/t-verter-n2-series/t-verter-n2-series_operation-manual_1072474055.webp)
52
Minute
(2) (1)
FIG. 4 1.0
150 % of motors operating current
Fn_71: Torque
Boost
xxx0:
Free run to stop after electronic thermal T-verter protection is energized
xxx1:
Operation continued after electronic thermal T-verter protection is energized
x0xx:
Torque Boost enable
x1xx:
Torque Boost disable
Fn_72: Torque compensation gain:
0.1 to 10 %
Note:
In (Fn_71) When using the setting (x1xx) Both Auto and Manual torque boost are inactive.
When using the setting (x0xx) the T-verter adjusts the torque boost by automatically
according to the T-verter’s output current.
When using the setting (x1xx) the Torque boost is adjusted according to the settings
in V/F pattern (Fn_05) and (Fn_72)
Fn_75:
Motors No Load Current - - - - -
Fn_76:
Motor rated slip:
0 - 6 Hz
Fn_77:
Over Torque Control
xxx0:
Over-torque detection disable
xxx1:
Over-torque detection enable
xx0x:
Enable only if at set freq.
xx1x:
Enable during operation
x0xx:
Operation continued after over-torque is detected
x1xx:
Free run to stop after over-torque is detected