38
Fn_24:
Jog Speed Reference
= 0 - 400 Hz
Fn_25: Master Speed Reference from Keypad = 0 - 400 Hz.
Note:
1.
The T-verter will be operating under the Jog Speed function at (Fn_24) you can assign either
(Fn_56) (Fn_57) or (Fn_58) to handle the jog function.
2.
The T-verter will operate under the Pre-set speed frequencies when (Fn_56) (Fn_57) or
(Fn_58) are assigned to this function.
3.
If the process timer in (Fn_84) is turned on and (Fn_56) (Fn_57) or (Fn_58) have been
assigned for input functions, if a pulse signal or contact closure is received on the
multi-function input, the T-verter will run at the pre-set time based on the setting in (Fn_85)
(Fn_86) (Fn_87) (Fn_88) (Fn_89) (Fn_90) and (Fn_91), The sequence will continue until all
process timers are finished, the T-verter will then returns to the frequency set by keypad or
an external Speed Pot or jump back to 0 speed to receive the next sequence.
4.
A New speed setting or timer sequence cannot be inserted during an active sequence.
Pre-set Speed
Terminal 6
Pre-set Speed
Terminal 7
Pre-set Speed
Terminal 8
Jog Terminal
Output
frequency (Hz)
Operation time
X X X X
Fn_25
O X X
X
Fn_17
Fn_85
X O X X
Fn_18
Fn_86
O
O
X
X
Fn_19
Fn_87
X X O
X
Fn_20
Fn_88
O X O X
Fn_21
Fn_89
X O O
X
Fn_22
Fn_90
O O O X
Fn_23
Fn_91
-- -- -- O
Fn_24
O: TERMINAL ON
X: TERMINAL OFF
--: NO EFFECT