8
Installation:
Location
Picking the proper installation location for the T-verter is imperative in order to achieve the
maximum specified performance & operation from the Drive. The T-verter should always be
installed in areas where the following conditions exist.
*
Good ambient operating temperature:
-10 to 40
℃
(14 to 104 F), -10 to 50
℃
(14 to 122 F) with cover removed
*
IP Rating: IP 20 for all models. If the T-verter is placed in another enclosure, please provide
addition cooling using an external fan.
*
Protected from rain & moisture.
*
Shielded from direct sunshine.
*
Free from metallic particles and corrosive gas.
*
Free from excessive vibration. (Below 0.5G)
Positioning
For effective ventilation and maintenance purposes, sufficient clearance (as shown in figure 2.1)
around the T-verter is necessary. The T-verter must be installed with heat sink ribs oriented
vertically.
z
Allow 12cm clearance on both
sides of the enclosure
z
Be sure to allow the air to move
freely through the heat sink
area.