24
Function
Fn_
xx
Description Set
Unit
Range
Factory
Setting
Page
31 Momentary power loss ride through time
0.1 sec
0-2 sec
0.5 sec
40
Momentary Power
Loss Ride Through 32 xxx0 : Disable xxx1 : Enable
0
40
Analog command
Scan Time
33 Tm2 terminal 13 Analog input
Scan time
1 1-100 100
40
34 Auto Restart Time
0.1 sec
0-800 sec
0 sec
41
Auto Restart
35 No. of Auto Restart Attempts
1
0-10
0
41
Motor poles
36 No. Of Motor Poles
2 P
2-72 pole
4P
41
37 Max. freq.
0.01 Hz
50-400 Hz
60 / 50
Hz*4
42
38 Max. voltage ratio
0.1%
0-100%
100%
42
39 Mid. freq.
0.01 Hz
0.11-400 Hz
3.0/2.5
Hz*4
42
40 Mid. voltage ratio
0.1%
0-100%
7.5 %
(6.5%)
42
V/F Pattern
41 Voltage ratio at 0.1 Hz
0.1%
0-100%
7.5%
(6.5%)
42
Starting freq.
42 Start freq. adjustment
0.01 Hz
0.1-10 Hz
1 Hz
42
Carrier freq.
43 Carrier freq. adjustment
1
0-15
14(12)
42
Stopping mode
44
xxx0 : Decel. to stop
xxx1 : Free run to stop
0000 43
45 Gain: Analog Output
1%
0-200 %
100%*1
43
Multi-function
Analog Output
Selection
(terminals)
(14 & 15)
46
0 : Output freq. (Fn 6 max.)
1 : Set freq. (Fn 6 max.)
2 : Output voltage
3 : DC voltage
0*1 43
Display mode
47
xxx0 : Output voltage (Vac) display disable
xxx1 : Output voltage (Vac) display enable
xx0x : DC voltage display disable
xx1x : DC voltage display enable
x0xx : Output current (Iac) display disable
x1xx : Output current (Iac) display enable
0000*1
43