4-32
Group4- Start/Stop command group
04-00 : Starting Method Selection
=0 : Normal start
=1 : Enable Speed Search
1.04-00=0: On starting, the inverter accelerates from 0 to target frequency in the set time.
2.04-00=1: On starting, the inverter accelerates to target frequency from the detected speed of
motor.
04-01 : Stopping Method Selection
=0: braking capacity
=1: Coast to stop
1.04-01=0 : the inverter will decelerate to 0Hz in preset deceleration time after receiving the stop
command.
2.04-01=1: the inverter will stop output as receiving the stop command. The motor will inertia
Coast to stop.
04-02 : Stop Key on keypad
=0 : Stop Button Enabled
=1 : Stop Button Disabled
04-02=0, The STOP key is available for controlling the inverter to stop.
04-03 : Momentary power loss and restart
=0 : Momentary Power Loss and Restart disable
=1 : Momentary power loss and restart enable
=2 : Momentary power loss and restart enable while CPU is operating.
(According to the capacity of DC power)
04-04 : Momentary Power Loss Ride-Thru Time (Seconds) : 0.0 ~ 2.0 second
1.If the input power supply due to sudden increase in supply demand by other equipment results in
voltage drops below the under voltage level, the inverter will stop output at once. If the power
supply voltage level recovers in the 04-04 preset time, it will spin start tracing from the trip
frequency, or otherwise the inverter will trip with ‘LV-C’ fault displayed.