ENGLISH
User’s manual
22
UPS EVO DSP MM RM
10
Technical Characteristics
UPS EVO DSP MM Rack Mount Model
6.0
10.0
Power
6000 VA
10000 VA
Nominal Active Power
4800 W
8000 W
Power Factor
0.8
Technology
On-Line Double Conversion Transformerless
Dimension (W x H x D) - UPS unit
43.8 x 13.3 x 58 cm
43.8 x 13.3 x 66.8 cm
Dimension (W x H x D) – Battery Box unit
43.8 x 13.3 x 66.8 cm
43.8 x 13.3 x 66.8 cm
Net Weight - UPS unit
17 kg
20 kg
Net Weight - Battery Box unit
57 kg
65 Kg
INPUT
Nominal Voltage
Single Phase 208/220/230/240 Vac
Voltage Range for
Normal mode
Lower Limit
110 Vac ± 3% (at 50% Load)
176 Vac ± 3% (at 100% Load)
Upper Limit
300 Vac ± 3%
Nominal Frequency
50/60 Hz (selectable)
Frequency Range (Normal mode)
± 7%
Input Power Factor
0.99 (at 100% Load)
OUTPUT
Nominal Voltage
Single Phase 208/220/230/240 Vac (selectable)
Voltage Regulation
±1%
Inverter Waveform
True Sinewave
Nominal Frequency
50/60 Hz (selectable)
Free Running Frequency (Battery mode)
(50 Hz ± 0.1%) or (60 Hz ± 0.1%)
Total Harmonic Distortion (THD)
< 3% (100% Linear Load); < 6% (100% Non-Linear Load)
Crest Factor
3:1 max
Overload (Normal mode)
(100÷110)% for 10 min; (110÷130)% for 1 min; > 130% 1 sec
Overload (Battery mode)
(100÷110)% for 30 sec; (110÷130)% for 10 sec; > 130% 1 sec
Transfer Time
(Normal <--> Battery)
0 ms
(Battery <--> Bypass)
0 ms
(Normal <--> Eco)
< 10 ms
Efficiency
> 89% (Normal mode); > 88% (Battery mode); > 98% (ECO mode)
BATTERIES (In External Battery Box gettable separately)
Battery Type
Lead acid, sealed, free maintenance
Number of batteries
20
Nominal Battery Voltage
240 Vdc
Battery Charge Time (typical)
8 hours
Expandable Autonomy
Available, through external Battery Box (optional)