Esempio:

 Se il certificato della bombo-

la indica il valore di 1,27%v/v 
(=25,4%LIE) Metano, il LIE del Metano 
è 5%v/v e si deve verificare un sensore 
Mod.TS292PX-S tarato per Butano va 
utilizzato il “

K

”=2,04 come indicato in 

Tab.3 per ottenere: 

mA

=






+

16 x 1,27

5

 x 2,04   4 = 12,29 

 

Exemple:

 If the test label on the sample 

gas bottle shows 1,27%v/v Methane 
(=25.4% LEL) and Methane’s LEL is 
5%v/v, to verify a detector model 
TS292PX-S calibrated for Butane, use 
the correspondig “

K

”=2,04, as shown in 

table 3, and the result will be: 

mA

=






+

16 x 1,27

5

 x 2,04   4 = 12,29   

Exemple :

 Si le certificat de la bouteille 

indique la valeur de 1,27%v/v 
(=25,4%LIE) Méthane et sa LIE est 
5%v/v et on doit verifier un capteur 
TS292PX-S étalonne pour butane, étant 
la valeur du “K” 2,04 comme indique 
dans le Tab. 3, le résultat sera: 

mA

=






+

16 x 1,27

5

 x 2,04   4 = 12,29   

 

 
 
 

Vdc

4-20mA

mA

Centrale rivelazione gas

Gas detector
Centrale de détection

RL

Fig.1 

Verifica

 / 

Test

 / 

Vérification

S

+

-

P3 “4mA”

P2 “

SPAN”

   

Fig.2 

Tester di calibrazione

Calibration Tester

Tester d’étalonnage

0,3L/min

EExd

D

 

 

Alimentazione / Power Supply / Alimentation

900

100

400

500

600

700

800

1000

50

12

24

0

0

4

13,8

28

10,8

200

Vdc

RL

RL=Resistenza di carico

Ohm

Load resistor

Resistance de charge

21,6

Fig.3 

Alimentazione / Resistenza di carico

Power supply / Load resistance diagram

Alimentation / Résistance de charge

    

Fig. 4

 

Dimensioni

Outline Dimensions / Dimensions

 

 

Summary of Contents for TS292P

Page 1: ...Pag 8 8 Istruzione User s Manual Manuel d utilisation IST 2292 PX01 01 A TECNOCONTROL S r l Via Miglioli 97 SEGRATE MI Tel 02 26 92 28 90 Fax 02 21 33 734 ...

Page 2: ...ltro sinterizzato certificato CESI Ex d IIC T6 posto nella parte inferiore della custodia I trasmettitori TS292P vengono normalmente collegati alle nostre centrali di rivelazione gas FUNZIONAMENTO L elemento sensibile utilizzato è un sensore catalitico Pellistor prati camente insensibile alle variazioni di umidità e temperatura DESCRIPTION The TS292P series consists of a three wire 4 20mA linear t...

Page 3: ...s a damage situation The same happens also when an interruption to the connec tion wires between the sensor and the detector occurs Average life The sensitive element used in this type of sensor has an exellent stability in time In fresh air and in normal working condition the sensor s life should be about 10 years from the date of the installa tion Periodical testing we advise to carry out workin...

Page 4: ...iso Butano 2 01 1 8 1 832 9 Alcool butilico terz tert Butyl alcohol 2 55 2 3 1 778 39 Iso pentano iso Pentano 0 62 1 4 2 300 10 Alcool butilico n n Butyl alcohol 2 55 1 4 3 042 40 Metano Methane 0 55 5 1 11 Alcool etilico Ethyl alcohol 1 59 3 5 1 691 41 Metilammina Methylamine 1 07 4 9 1 250 12 Alcool isobutilico iso Butyl alcohol 2 55 1 68 2 541 42 Metilcicloesano Methylcyclohexane 3 4 1 1 2 559 ...

Page 5: ...ll be mA 16 x 1 27 5 x 2 04 4 12 29 Exemple Si le certificat de la bouteille indique la valeur de 1 27 v v 25 4 LIE Méthane et sa LIE est 5 v v et on doit verifier un capteur TS292PX S étalonne pour butane étant la valeur du K 2 04 comme indique dans le Tab 3 le résultat sera mA 16 x 1 27 5 x 2 04 4 12 29 Vdc 4 20mA mA Centrale rivelazione gas Gas detector Centrale de détection RL Fig 1 Verifica T...

Page 6: ...s Some other substances produce a temporary loss of sensitivity These inhibitors include Hydrogen sul fide Chlorine Chlorinated hydro carbons and halohenated com pounds The sensitivity is recovered after a short period of running in clear air Very Important Pellistor sensors will operate up to 100 LEL and can function only in presence of Oxy gen Do not use pure gases or a lighter directly on the s...

Page 7: ...and LEL TS292PX S Model TS292PX S is able to detect combustibles gases up to 100 LEL It employs a Pellistor sensor calibrated for the gases listed in Table 1 If other gases not listed in this table are present in the environment we suggest to use the model TS2932PX H Tab E shows the correspondence be tween mA output signal and LEL TS292PX H Model TS292PX H is able to detect combustibles gases up t...

Page 8: ...mperometer indi cates 4mA 0 1 If necessary turn the P3 potentiometer as long as the required value is not reached Full scale calibration To verify or and calibrate an instrument use a sample bottle with the specific gas air mixture which had been used to cali brate the instrument Connect the sample gas bottle Fig 2 to the flow meter set the flowmeter on a 0 15 0 3 l min flow rate wait for 3 minute...

Reviews: