TFA2-596 - TFA4-1192
49
Power Supply:
ALSW285PFC
Input voltage: 230V
~ +10%-15% 50/60Hz
Max input current: 700mA
Output: 28,2V — I max: 5A
Further information on the technical manual
INPUT
OUTPUT
N
L
Power Supply: ALSW285PFC
Input voltage: 230V~ +10%-15% 50/60Hz
Max input current: 700mA
Output: 28,2V — I max: 5A
Further information on the technical manual
INPUT
OUTPUT
N L
1
2 3
CSV
A
1
2
N
3
L
B
C
D
E
F
A
B C
D
F
E
The control panels are equipped with a Fly-back type switching power supply model ALSW285PFC providing a maximum output
current of 5A @ 24V DC (default calibration 28.8V DC @ 25°C). The power supply is equipped with an integrated PFC circuit
(Power Factor Correction) which interrupts current supply when there is no power demand. Therefore the power supply only starts
working with a load superior to 50mA. The connection to the control panel is made via a polarized connector. The wiring transfers
to the control panel the power supply as well as diagnostic.
N.B.
The voltage value measured at the battery charger output is subject to variations, due to the temperature of the battery.
The battery temperature is measured by a probe mounted on the battery surface.
Input protection
The 230V AC mains input is protected against overvoltage by varistors and by a non replaceable fuse integrated in the electronics
(F1:T1.6A - T). Fuse blowing is necessarily attributed to a failure, or an exceptionally violent electromagnetic discharge that would
inevitably require repair.
Output protection
The output section of the power supply is automatically protected against short circuits and overloads. If one of these conditions
occurs, the device deactivates and then reactivates automatically when the cause of the cut-off is removed or normal operating
conditions are restored.
9-6 - Power supply
Current
Blow time
1.5A
Approx. 1 hour
2A
Approx. 2 minutes
4A
150ms to 3 seconds
Terminals
Ground connector
Neutral conductor 230V AC
Phase conductor 230V AC
LED
Green
On = normal operating conditions
Battery check probe connection
Pre-wired polarized control panel connector
Mounting holes for
fi
xing to control panel casing
Summary of Contents for Tecnofire TFA2-596
Page 2: ...TFA2 596 TFA4 1192 2...
Page 4: ...TFA2 596 TFA4 1192 4...
Page 10: ...TFA2 596 TFA4 1192 10...
Page 14: ...TFA2 596 TFA4 1192 14...
Page 28: ...TFA2 596 TFA4 1192 28...
Page 32: ...TFA2 596 TFA4 1192 32...
Page 40: ...TFA2 596 TFA4 1192 40...
Page 50: ...TFA2 596 TFA4 1192 50...
Page 62: ...TFA2 596 TFA4 1192 62 NOTES...
Page 63: ......