TFA2-596 - TFA4-1192
30
7-1 - Failure noti
fi
cations of the power supply section
TABLE 1 - PRIMARY POWER SUPPLY FAILURE
The test is performed every second. The failure is noti
fi
ed when for the preset time the mains power is missing.
Test frequency
1 second
Delay of failure noti
fi
cation
Programmable from 0 to 30 minutes
Signaling on occurence of failure
The
MAINS PWR OK
LED turns off
The
PWR SPLY FAILURE
LED
fl
ashes
Signaling on noti
fi
cation of failure
The control panel display shows
MAINS
FAILURE
The failure noti
fi
cation is stored in the failure folder and the relative counter is incremented
The
PWR SPLY FAILURE
LED turns on steadily
The
GENERAL FAILURE
LED starts
fl
ashing
The failure relay is activated
Reset of faillure noti
fi
cations
The failure noti
fi
cations are reset after detecting for the preset time, that the mains power voltage has been restored.
N.B.
The MAINS PWR OK LED follows the state of mains power immediately without any delay.
TABLE 3 - BATTERY HIGH IMPEDANCE
The test is performed only in the presence of mains power, with an interval of 30 minutes, on each battery.
The failure is noti
fi
ed if the test detects an impedance above the failure threshold (1,5
Ω
which cannot be changed).
Test frequency
30 minutes
Delay of failure noti
fi
cation
2 hours
Signaling on occurence of failure
The
BATTERY
LED starts
fl
ashing
Signaling on noti
fi
cation of failure
The control panel display shows
BATTERY
FAILURE
The failure noti
fi
cation is stored in the failure folder and the relative counter is incremented
The
BATTERY
LED turns on steadily
The
GENERAL FAILURE
LED starts
fl
ashing
The failure relay is activated
Reset of faillure noti
fi
cations
The failure noti
fi
cations are reset after detecting, for 30 seconds, that the impedance of the battery has returned to
a value below the failure threshold.
TABLE 2 - SECONDARY POWER SUPPLY FAILURE
The test is performed only in the presence of mains power, with an interval of 10 seconds, on each battery.
The failure is noti
fi
ed if the test detects for 5 minutes a battery voltage without load below 10V.
Test frequency
10 seconds
Delay of failure noti
fi
cation
5 minutes
Signaling on occurence of failure
The
BATTERY
LED
fl
ashes
Signaling on noti
fi
cation of failure
The control panel display shows
BATTERY
FAILURE
The failure noti
fi
cation is stored in the failure folder and the relative counter is incremented
The
BATTERY
LED turns on steadily
The
GENERAL FAILURE
LED starts
fl
ashing
The failure relay is activated
Reset of faillure noti
fi
cations
The failure noti
fi
cations are reset after detecting, for 30 seconds, a battery voltage without load above 10V
Summary of Contents for Tecnofire TFA2-596
Page 2: ...TFA2 596 TFA4 1192 2...
Page 4: ...TFA2 596 TFA4 1192 4...
Page 10: ...TFA2 596 TFA4 1192 10...
Page 14: ...TFA2 596 TFA4 1192 14...
Page 28: ...TFA2 596 TFA4 1192 28...
Page 32: ...TFA2 596 TFA4 1192 32...
Page 40: ...TFA2 596 TFA4 1192 40...
Page 50: ...TFA2 596 TFA4 1192 50...
Page 62: ...TFA2 596 TFA4 1192 62 NOTES...
Page 63: ......