17/04/2019
–
TPF-Eco version u111
▪
48 hour -> Switches to anti-frost
•
CF10
–
Value of the maximum comfort setting
o
Use + and
–
to adjust from 22
–
30 °C
•
CF11
–
Programming intervals
o
0 = 1 hour steps (default)
o
1 = ½ hour steps
•
CF12
–
Time display format
o
0 = 12 hour AM/PM
o
1 = 24 hour (default)
•
CF13
–
Automatic change to summer/winter time
o
0 = Disabled
o
1 = Enabled (default)
o
If this is disabled, the thermostat will not ask you to set the date when set the time.
•
CF15
–
Display of the open window symbol when there’s
an open window event
o
0 = Symbol steady
o
1 = Symbol flashes (default)
•
CF16
–
Display of the “currently heating” symbol
o
0 = Disabled
o
1 = Enabled (default)
•
CF17
–
Display of the presence
symbol when there’s a presence detection event
o
0 = Symbol steady
o
1 = Symbol flashes (default)
•
CF18
–
Display energy consumption
o
0 = Disabled (default)
o
1 = Enabled
o
The thermostat will then allow you to associate a wattage with each of the paired
panels.
▪
Shows you each panel in turn (P01, P02 etc.)
▪
Use +/- keys to adjust the wattage and press OK to go to the next panel.
o
You can tell which panel you are setting because its receiver will “tick” when you’re
on the screen for that panel. (Latest versions of receiver only).
Later versions of the TPF-Eco
–
software version u111 and onward
–
also include the following
options:
•
CF28
–
Anticipation function (adaptive start)
o
0 = Disabled
o
1 = Enabled (default)
•
CF29
–
Anticipation sensitivity
o
Use +/- keys to adjust from 1 °C to 6 °C. (default = 3 °C)
o
This setting allows you to adjust the anticipation parameters depending on the
behaviour of the room. If the room is getting hot too early, increase the sensitivity to
a higher number of degrees. If the room is getting hot too late, decrease the
sensitivity to a smaller number of degrees.
•
CF30
–
Display of room temperature in shutdown mode
o
0 = Disabled
o
1 = Enabled (default)