iPOS4808 BX-CAN Technical Reference
. shows the recommended spacing to assure proper airflow by natural convection,
in the
worst case
– closed box done from a plastic (non-metallic) material with no ventilation openings.
Whenever possible, ventilation openings shall be foreseen on the top side wall or the box and at
the bottom of the lateral walls. When using a horizontal support considerably larger than the size
of the hosted iPOS4808 BX-CAN drives, it is recommended to provide ventilation holes in the
support also.
Remark: In case of using a metallic box, with ventilation openings, all spacing values may be
reduced substantially. With proper ventilation, keeping the air surrounding the iPOS4808 BX-CAN
inside the limits indicated, the spacing values may be reduced down to zero
.
Figure 3.2 Recommended spacing for vertical mounting, worst case: non-metallic, closed box
If ventilation driven by natural convection is not enough to maintain the temperature surrounding
the iPOS4808 BX-CAN drive(s) inside the limits indicated, then alternate forced cooling methods
must be applied.