Outputs
22
Outputs status of the analogue outputs
For the output status you can define whether the ON status should be is
-
sued above or below an adjustable threshold.
Example:
If the analogue output is over 3.00 V, the output status switches from OFF to ON.
Depending on the technical attributes of the pump being controlled, it
may thus be possible to set the output status to be ON only when the
pump is actually running.
If you want an analogue output (A7 – A10) to be switched
together with
a switching output, it can
only be done by means of appropriate programming.
Example:
As soon as the output status of the analogue output switches to ON, that ON command is
forwarded to the switching output via the logic function.