Inputs
16
Designation
Enter the input designation by selecting a predefined designation from various designation groups
or from the user defined designations.
Sensor type Analogue / Temperature:
• General
• Generator
• Consumer
• Line
• Climate
•
User
(user defined designations)
You can also assign a number from 1 to 16 to every designation.
Sensor correction
The option of sensor correction is available for the measured variables Temperature, Solar radiation,
Humidity and Rain. The corrected value is utilised for all calculations and displays.
Example:
PT1000 temperature sensor
Average
This setting refers to the average of the measurements
over time.
Averaging over 0.3 seconds leads to extremely rapid reactions on the part of the display and the unit.
However, this can be expected to cause fluctuations of the value.
A large average value leads to inertia and is only recommended for sensors for the heat meter.
For simple measuring tasks, around 1 - 3 seconds should be selected. For hygienic domestic hot wa
-
ter heating with the ultra-fast sensor, 0.3 - 0.5 seconds should be selected.