Heat meter
36
Output variables
Output
Display of the current thermal output in kW (to two decimal places)
Corrected return
temperature
Display of the return temperature corrected by the calibration pro
-
cess
Differential
(Tflow-Trtn corr)
Display of the current temperature differential between the flow and
corrected return temperature, which is critical for the heat meter
Day meter reading
Meter readings
Prev. day meter reading
Week meter reading
Prev. week meter reading
Month meter reading
Prev. month meter reading
Year meter reading
Prev. year meter reading
Kilowatt hours total
Day sum
Display of yield in the set currency
Previous day sum
Week sum
Prev. week sum
Month sum
Prev. month sum
Year sum
Prev. year sum
Sum total
•
ATTENTION:
The meter readings from the Heat meter function module are saved to the inter
-
nal memory every hour. Therefore, in the event of a power failure, no more than 1 hour of
metering can be lost.
• When loading function data, you will be asked whether you want to apply the saved counter
readings (see manual Programming Part 1: General information).
• If the flow temperature is lower than the return temperature, the meter will count
negative
energy if the reversing lock is set to
No.
The meter reading will be
reduced
as a result.
• The changeover of the Week meter occurs on Sundays at 24:00 h.