![Technische Alternative CAN-EZ2 Manual Download Page 71](http://html1.mh-extra.com/html/technische-alternative/can-ez2/can-ez2_manual_1069709071.webp)
71
CAN digital outputs
Up to 32 CAN digital outputs can be programmed. They are defined by specifying the source in the
controller.
Their parameters are programmed in exactly the same way as for the CAN analogue outputs except
for the transmission conditions.
Designation and transmission condition
Every CAN digital output can be given its own designation. The designation can be selected from var
-
ious designation groups or can be user defined, as for the inputs.
Example:
Transmission condition
Example:
Active CAN nodes
If Back is pressed in the main menu view, the network overview opens. All
active CAN nodes with node number and device designation are displayed
here. Select an x2 device to be able to access it.
This view shows a CAN-EZ3 with node number 32 in the CAN bus network,
and a C.M.I. with node number 1. To return to the menu of the energy me
-
ter, select the energy meter itself (e.g.:
32: CAN-EZ3
) in this overview.
If change Yes/No
Transmission of the value if a status change occurs
Blocking time 10 s
If the value changes within 10 seconds of the last transmission, the
value is nevertheless only transmitted again after 10 seconds (mini
-
mum setting: 1 sec.).
Interval time 5 m
The value is transmitted every 5 minutes even if it has not changed
since the last transmission (minimum setting: 1 minute).
Summary of Contents for CAN-EZ2
Page 5: ......
Page 62: ...62 Messages This menu item displays activated messages Example A message is active...
Page 98: ......
Page 99: ......