Page 28 • MN06150 ║ Issue/Rev. 0.7 (9/18)
Section IV – Diagrams
Figure 15. Multiple microLoad.net Serial Communications
The figure shows the typical wiring scheme for multi-drop communications between a communications device and
multiple microLoad.nets. The last microLoad.net in a multi-drop scheme must have the Receive Terminators enabled.
These terminators are asserted by placing the appropriate switches of “S1” to the “ON” position. See Page 14 for
location of “S1” on the MNET board.
• COM 1 Terminators: switches 1 and 2
• COM 2 Terminators: switches 3 and 4
• COM 3 Terminators: switches 5 and 6
Note:
These terminators are for EIA-485 communications only. DO NOT assert terminators for EIA-232 modes.