background image

5

CURRENT

4.2.3 -  REMOTE CONTROL

• The unit is factory-wired for heating mode operation. Operating control of unit is possible by connecting 2 potential-free, high-

quality external switches (not included):

- 1 for the remote On/Off signal(contact closed = operation authorized, contact open = off),
- 1 for change-over of the operating mode (contact closed = heating mode, contact open = cooling mode).

• The On/Off signal is connected to terminals 1 and 2 of the PCB located in the switch box (remove the existing bridge - see

diagram).

• The mode change-over signal is connected to terminals 3 and 4 of the PCB (remove the existing bridge - see diagram).
• The wiring of these contacts must not be routed near power cables in order to avoid electromagnetic disturbances.
• Use shielded cable.
• Max. connection cable length: 20 m.
• Minimum wire size: 0.25 mm

2

.

2

1

3

4

PMERV

6

1

2

5

Remote control

K 60 D 035 Z

WARNING:

Mode changes (heating/cooling) are to be performed
with the unit shutdown.

Remote control "off"

Operating mode

(

)

(

)

2

1

3

4

PMERV

(

)

(

)

(

) Jumper to be removed

The "Remote control unit, K 60 D 035 Z" can perform this
function.

4.2.4 - MISCELLANEOUS

• Alarm transfer:

Potential-free, closing contact ( 2A - 250 VAC max.) located on the PMERV terminal board (terminals 5 and 6 of the PCB)
for remote signaling.  See electrical diagrams.

• Water circulating pump control:

Do not use this contactor for the underfloor "Heating/cooling" application.

4.2.5 - PCB CONNECTION DETAILS

• Note: The terminals are of the "cage with spring" type.

Follow the indications below to connect them.
- These terminals take the following wires:

. rigid,
. flexible (avoid splicing the strands!),
. with ends.

- A single conductor per securing point.
- Make sure that the wires are correctly connected to the terminal board.

Incorrect connection can cause operating problems as well as overheating
which can cause fires.

3

1

2

Remote control "off"

Operating mode

(

) Jumper to be removed

Nominal current

A

Max. current

A

Starting current

A

7.8
9.6

45

6.4

8

45

COOLING mode

HEATING mode

Summary of Contents for PMERV 5

Page 1: ...1 10 11 338 GB 06 April 2004 PMERV 5 AIR COOLED WATER CHILLER HEAT PUMP R 407 C refrigerant INSTALLATION INSTRUCTIONS...

Page 2: ...ed for the R 407 C fluid 3 The weight of the refrigerant contained in the storage bottle must be checked constantly Do not use it from the moment the remaining weight is less than 10 of the total weig...

Page 3: ...ect s technical file The personnel responsible for receiving the unit must conduct a visual inspection in order to identify all damage to which the unit may have been subjected during transport refrig...

Page 4: ...ion The electrical connection conduits must be fixed Use the cable clamps located inside the switch box Class 1 unit The electrical installation must comply with the standards and regulations applicab...

Page 5: ...anges heating cooling are to be performed with the unit shutdown Remote control off Operating mode 2 1 3 4 PMERV Jumper to be removed The Remote control unit K 60 D 035 Z can perform this function 4 2...

Page 6: ...2 220 Ohmic value Ohm 24 VAC SUPPLY TRANSFORMER CARTE ELECTRONIQUE A MICROPROCESSEUR CHILLER COMPACT ACTUATORS DIGITAL INPUTS Temperature probe S1 for control Temperature probe S2 for defrosting and p...

Page 7: ...continue to function for a certain amount of time 150 seconds max PRG mute SEL chiller 5 sec comp x 100 PRG mute SEL chiller the PRG 1 key If during the adjustment procedure no key is pressed for 60 s...

Page 8: ...s if necessary see table below Remedy the fault Important note any work must be done by qualified experienced person The alarm is cancelled automatically when the fault is cleared NOTE If the circulat...

Page 9: ...e properly tight and that the hydraulic circuit functions correctly purge of circuits position of valves hydraulic pressure That there are no leaks That the machine is stable That the power cables are...

Page 10: ...MPORTANT NOTE Before carrying out any work on the machine make sure that it is switched off and that access to it is prevented Any work must be carried out by personnel qualified and authorised to wor...

Page 11: ...olours of the wires B Blue BW Blue White G Grey GN Grey Black L Purple M Brown MR Brown Red N Black NB Black Blue NL Black Purple NM Black Brown P Pink PG Pink Grey R Red RG Red Grey RL Red Purple RW...

Page 12: ...eux BP 131 01601 Tr voux CEDEX France Tel 33 4 74 00 92 92 Fax 33 4 74 00 42 00 R C S Bourg en Bresse B 759 200 728 Due to our policy of continuous development our products are liable to modification...

Reviews: