background image

9

5.8.6 - DEFROSTING (In heating mode only)

• The control is regulated to operate as follows:

- If the temperature detected by probe S3 is less than -3

°

C (for at least 10 seconds), the machine starts de-icing (switching

of cooling cycle and stopping of fan) until the temperature read by S3 rises to +7

°

C. (However, the duration of a de-icing phase

is limited to 10 minutes. If de-icing is stopped by this time delay, alarm "r1" appears on the display).
A period of 40 minutes must pass before a new de-icing phase can start.
For special operating conditions, it may be necessary to change these settings. In this case, contact the after sales service.

NOTE: Message "d1" appears on the display during the defrosting phase.

5.8.7 - CYCLE INVERSION VALVE

• The valve is activated in cooling mode.

6 - STARTING

IMPORTANT NOTE

Before carrying out any work on the machine, make sure that it is switched off and that access to it is prevented.

Any work must be carried out by personnel qualified and authorised to work on this type of machine.

6.1 - CHECK:

• That hydraulic connections are properly tight and that the hydraulic circuit functions correctly:

- purge of circuits,
- position of valves,
- hydraulic pressure.

• That there are no leaks.
• That the machine is stable.
• That the power cables are well fixed to their connection terminals. Terminals that are poorly tightened may cause overheating

and malfunctions.

• That the electric cables are well insulated from any sections of sheet metal or metal parts which could damage them.
• That probe, control and power cables are properly separated.
• That the machine is earthed.
• That there are neither tools nor other foreign objects in the units.

6.2 - STARTING-UP THE UNIT

• Turn the water on.
• Power up the unit.
• Start the appliance (see previous paragraph).

6.3 - CHECKS TO BE MADE

• Water flow-rate.

Note: The PMERV water output must be permanent (particular attention should be paid in the case of control of the terminal

units on 2-way valve).

• Hydraulic circuit pressures.
• Cooling circuit pressures.
• Control system operation.

IMPORTANT:
• If antifreeze is added (monopropylene glycol), a minium rate of 15% to 20% is needed to avoid any risk of corrosion.
• The LP controller (standard, factory installed) cuts off at 0.5 bar (automatic reset).
• The HP controller (accessory, not factory installed) cuts off at 29 bar (manual reset).

Summary of Contents for PMERV 5

Page 1: ...1 10 11 338 GB 06 April 2004 PMERV 5 AIR COOLED WATER CHILLER HEAT PUMP R 407 C refrigerant INSTALLATION INSTRUCTIONS...

Page 2: ...ed for the R 407 C fluid 3 The weight of the refrigerant contained in the storage bottle must be checked constantly Do not use it from the moment the remaining weight is less than 10 of the total weig...

Page 3: ...ect s technical file The personnel responsible for receiving the unit must conduct a visual inspection in order to identify all damage to which the unit may have been subjected during transport refrig...

Page 4: ...ion The electrical connection conduits must be fixed Use the cable clamps located inside the switch box Class 1 unit The electrical installation must comply with the standards and regulations applicab...

Page 5: ...anges heating cooling are to be performed with the unit shutdown Remote control off Operating mode 2 1 3 4 PMERV Jumper to be removed The Remote control unit K 60 D 035 Z can perform this function 4 2...

Page 6: ...2 220 Ohmic value Ohm 24 VAC SUPPLY TRANSFORMER CARTE ELECTRONIQUE A MICROPROCESSEUR CHILLER COMPACT ACTUATORS DIGITAL INPUTS Temperature probe S1 for control Temperature probe S2 for defrosting and p...

Page 7: ...continue to function for a certain amount of time 150 seconds max PRG mute SEL chiller 5 sec comp x 100 PRG mute SEL chiller the PRG 1 key If during the adjustment procedure no key is pressed for 60 s...

Page 8: ...s if necessary see table below Remedy the fault Important note any work must be done by qualified experienced person The alarm is cancelled automatically when the fault is cleared NOTE If the circulat...

Page 9: ...e properly tight and that the hydraulic circuit functions correctly purge of circuits position of valves hydraulic pressure That there are no leaks That the machine is stable That the power cables are...

Page 10: ...MPORTANT NOTE Before carrying out any work on the machine make sure that it is switched off and that access to it is prevented Any work must be carried out by personnel qualified and authorised to wor...

Page 11: ...olours of the wires B Blue BW Blue White G Grey GN Grey Black L Purple M Brown MR Brown Red N Black NB Black Blue NL Black Purple NM Black Brown P Pink PG Pink Grey R Red RG Red Grey RL Red Purple RW...

Page 12: ...eux BP 131 01601 Tr voux CEDEX France Tel 33 4 74 00 92 92 Fax 33 4 74 00 42 00 R C S Bourg en Bresse B 759 200 728 Due to our policy of continuous development our products are liable to modification...

Reviews: