background image

8

0

U

22°C

40°C

50°C

5.8 - SPECIAL OPERATING FEATURES

5.8.1 - ANTI-FREEZE PROTECTION OF WATER HEAT EXCHANGER

• 2 functions performed:

- control of a heating resistor,
- anti-freeze alarm stopping the machine.

• Operating diagram (see opposite).

Freeze alarm

Resistor control

Max. voltage

Min.

voltage

Condensing
temperature

2°C

1°C

0°C

3°C

4°C

0

1

1

0

0

The setting of these thresholds can be changed in the factory on request to suit the machine’s operating conditions.

5.8.2 - REMOTE CONTROL

• Do not use this contactor for the "Heating/cooling floor" application.

5.8.3 - REMOTE CONTROL

• See details in paragraph 4.2.3.

5.8.4 - POWER CUT

• If the power is cut to the control circuits, the electronic control unit returns to the operating mode it was in before the power was

cut and the parameters are still stored in memory when the power is restored.

5.8.5 - HEAD PRESSURE CONTROL

• The PMERV 5 comes with a factory-installed specific voltage control

board, controlled directly by the 

µ

CHILLER electronic control device.

• On the basis of temperature information (taken by the probe S3 located on

the condenser), the control unit varies the fan’s supply voltage according
to the diagram opposite.

• This system is operational in cooling mode.

SUMMARY TABLE OF ALARMS

(*) Factory settings

5.7 - ALARMS

• When an alarm occurs:

- the bell rings (2 A closing contact - 250 VAC max.),
- the display flashes and the alarm message appears cyclically (see table below),
- the machine stops if necessary (see table below).

• Remedy the fault.

Important note: any work must be done by qualified, experienced person.

• The alarm is cancelled automatically when the fault is cleared.

NOTE: If the circulation pump control is used, the "Water output" alarm may need to be reset manually by simultaneously pressing
the  

 (2) and  

 (3) keys.

• At that moment:

- the alarm report is de-activated,
- the display reverts to normal (no flashing),
- the machine can re-start (if it was stopped).

Fault on probe 1

Fault on probe 2

Fault on probe 3

Water flow rate

H.P. (unused)
L.P.
Water heat exchanger frozen

Defrosting too long

Compressor maintenance

Memory error

Min. voltage
supply control

Max. voltage
supply control
Interference on
supply control

E1

E2

E3

FL

H1

L1

A1

r1

n1

EE
EP

EU

EO

EL

-

-

-

30" on start-up

10" in operation

-

150" on start-up

-

-

-

-

-

-

-

-

-

-

-

Pressure switch
Pressure switch

2

°

C

10 mn

10 000 h

-

-

-

-

Auto

Auto

Auto

Auto

Auto
Auto
Auto

Auto

Manual

According

to

seriousness

of fault

Auto

Auto

Auto

X

X

X

X

X
X
X

-

According

to

seriousness

of fault

According to

seriousness

of fault

X

-

X

-

According

to

seriousness

of fault

According to

seriousness

of fault

X

-

X

X

X

X

X
X
X

-

According

to

seriousness

of fault

According to

seriousness

of fault

X

-

Actuates anti-freeze
resistors

Alarm enabled if pump
running
Fan time delay, stopped 1’

Self-cancellation with
correct defrosting cycle

After-sales department
operation to renew
parameters or change
the electronics

Ventilation
on high speed

Inhibition

delay (*)

Threshold

(*)

Machine

stop

Pump

stop

Cancellation

Report

Remarks

Alarm

Message

NOTE: The alarms are not activated when the machine is off (except for probe and memory faults).

Summary of Contents for PMERV 5

Page 1: ...1 10 11 338 GB 06 April 2004 PMERV 5 AIR COOLED WATER CHILLER HEAT PUMP R 407 C refrigerant INSTALLATION INSTRUCTIONS...

Page 2: ...ed for the R 407 C fluid 3 The weight of the refrigerant contained in the storage bottle must be checked constantly Do not use it from the moment the remaining weight is less than 10 of the total weig...

Page 3: ...ect s technical file The personnel responsible for receiving the unit must conduct a visual inspection in order to identify all damage to which the unit may have been subjected during transport refrig...

Page 4: ...ion The electrical connection conduits must be fixed Use the cable clamps located inside the switch box Class 1 unit The electrical installation must comply with the standards and regulations applicab...

Page 5: ...anges heating cooling are to be performed with the unit shutdown Remote control off Operating mode 2 1 3 4 PMERV Jumper to be removed The Remote control unit K 60 D 035 Z can perform this function 4 2...

Page 6: ...2 220 Ohmic value Ohm 24 VAC SUPPLY TRANSFORMER CARTE ELECTRONIQUE A MICROPROCESSEUR CHILLER COMPACT ACTUATORS DIGITAL INPUTS Temperature probe S1 for control Temperature probe S2 for defrosting and p...

Page 7: ...continue to function for a certain amount of time 150 seconds max PRG mute SEL chiller 5 sec comp x 100 PRG mute SEL chiller the PRG 1 key If during the adjustment procedure no key is pressed for 60 s...

Page 8: ...s if necessary see table below Remedy the fault Important note any work must be done by qualified experienced person The alarm is cancelled automatically when the fault is cleared NOTE If the circulat...

Page 9: ...e properly tight and that the hydraulic circuit functions correctly purge of circuits position of valves hydraulic pressure That there are no leaks That the machine is stable That the power cables are...

Page 10: ...MPORTANT NOTE Before carrying out any work on the machine make sure that it is switched off and that access to it is prevented Any work must be carried out by personnel qualified and authorised to wor...

Page 11: ...olours of the wires B Blue BW Blue White G Grey GN Grey Black L Purple M Brown MR Brown Red N Black NB Black Blue NL Black Purple NM Black Brown P Pink PG Pink Grey R Red RG Red Grey RL Red Purple RW...

Page 12: ...eux BP 131 01601 Tr voux CEDEX France Tel 33 4 74 00 92 92 Fax 33 4 74 00 42 00 R C S Bourg en Bresse B 759 200 728 Due to our policy of continuous development our products are liable to modification...

Reviews: