Power Source
220–240V ~ 50Hz
Voltage rating
230 V
Performance
Cooling
Heating
Capacity
kW
3.35
3.90
BTU/h
11,424
13,299
Air circulation (High) m
3
/h 700
Moisture removal (High)
Liters/h
1.3
—
Electrical Rating
Cooling
Heating
Available voltage range
V
198 ~ 264
Running amperes
A
5.6
6.1
Power input
W
1,220
1,320
Power factor
%
95
94
C.O.P.
W/W
2.7
3.0
Compressor locked rotor amperes
A
34
34
Features
Controls / Temperature control
Microprocessor / I.C. thermostat
Control unit
Wireless remote control unit
Timer
ON/OFF 24 hours & Daily program,1-hour OFF
Fan speeds
Indoor / Outdoor
3 and Auto / 1(Hi)
Airflow direction (Indoor)
Horizontal
Manual
Vertical
Auto
Air filter
Washable, Anti-Mold
Compressor
Rotary (Hermetic)
Refrigerant / Amount charged at shipment g R22 / 1260
Refrigerant control
Capillary tube
Operation sound Indoor : Hi / Me / Lo dB-A 44 / 40 / 35 44 / 40 / 35
Outdoor : Hi
dB-A
45
47
Refrigerant tubing connections
Flare type
Max. allowable tubing length at shipment
m
7.5
Refrigerant
Narrow tube
mm (in.)
6.35(1/4)
tube diameter
Wide tube
mm (in.)
12.7(1/2)
Refrigerant tube kit / Accessories
Optional / Air Clean Filter
Dimensions & Weight
Indoor Unit
Outdoor Unit
Unit dimensions Height mm 680 540
Width mm 900 700
Depth mm 190 265
Package dimensions Height mm 813 568
Width mm 1,011 815
Depth mm 296 343
Weight Net kg 23.5 38.0
Shipping kg 30.0 41.0
Shipping volume m
3
0.24 0.16
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Remarks:
Rating conditions are:
Cooling : Indoor air temperature 27°C D.B. / 19°C W.B.
Outdoor air temperature 35°C D.B. / 24°C W.B.
Heating : Indoor air temperature 20°C D.B.
Outdoor air temperature 7°C D.B. / 6°C W.B.
Indoor Unit KPA128R5TAA
Outdoor Unit GR129R5TBA