27
6. ELECTRICAL DATA
6-1. Electrical Characteristics
Indoor Unit MCAV77R5VAA
Outdoor Unit GR79R5TBA
COOLING
Indoor Unit Outdoor Unit Complete Unit
Fan Motor Fan Motor Compressor
Performance at 230V 1-phase 50Hz
Rating Conditions Running Amps. A 0.11 0.24 3.35 3.7
Power Input kW 0.025 0.055 0.710 0.790
Full Load Conditions Running Amps. A 0.11 0.24 4.05 4.4
Power Input kW 0.025 0.055 0.89 0.97
Rating Conditions : Indoor Air Temperature 27°C D.B. / 19°C W.B.
Outdoor Air Temperature 35°C D.B.
Full Load Conditions : Indoor Air Temperature 32°C D.B. / 23°C W.B.
Outdoor Air Temperature 43°C D.B.
HEATING
Indoor Unit Outdoor Unit Complete Unit
Fan Motor Fan Motor Compressor
Performance at 230V 1-phase 50Hz
Rating Conditions Running Amps. A 0.11 0.24 3.15 3.5
Power Input kW 0.025 0.055 0.671 0.75
Full Load Conditions Running Amps. A 0.11 0.24 3.2 3.55
Power Input kW 0.025 0.055 0.690 0.770
Rating Conditions : Indoor Air Temperature 20°C D.B.
Outdoor Air Temperature 7°C D.B. / 6°C W.B.
Full Load Conditions : Indoor Air Temperature 27°C D.B.
Outdoor Air Temperature 24°C D.B. / 18°C W.B.